Danfoss EKC 312 User Manual Download Page 11

© Danfoss A/S (DCS-IMCGPD/sw), 2015-03    

 

 

DKRCC.PS.R1.A3.02 / 520H9752 

 

11

Manual 

Electronic superheat controller, type EKC 312

Appendix 4

Regulation algorithms for the superheat. (loop ctrl.).

There are two algorithms to choose between. 

They are set in ”o56”.

Loop Ctrl.=1

This regulation algorithm is used for the classical method 

and is recommended for known applications – e.g. for earlier 

installations with a Danfoss controller. For a start the values 

for Kp, and Tn can be set to values corresponding to the earlier 

ones.

 

Loop Ctrl. =2

This setting is recommended if only one regulation of the 

superheat is required.

The regulation algorithm necessitates the mounting of a 

temperature sensor in the media.

The S4 and T0 temperatures also form part of an inner loop 

regulation.

Start of controller

When the electric wires have been connected to the controller, 

the following points have to be attended to before the regulation 

starts:

1. Switch off the external ON/OFF switch that starts and stops the 

regulation

2. Follow the menu survey on page 6, and set the various 

para-meters to the required values

3. Switch on the external switch, and regulation will start

4. Follow the actual superheat on the display

If the superheating fluctuates

When the refrigerating system has been made to work steadily, 

the controller’s factory-set control parameters should in most 

cases provide a stable and relatively fast regulating system.

If the system however fluctuates this may be due to the fact that 

too low superheat parameters have been selected:

Adjust: n09 and n10.

Alternatively it may be due to the fact that the set regulation 

parameters are not optimal.

If the time of oscillation is longer than the integration time:

(T

p

 > T

n

 , (T

n

 is, say, 240 seconds))

1. Increase T

n

 to 1.2 times T

p

2. Wait until the system is in balance again

3. If there is still oscillation, reduce K

p

 by, say, 20%

4. Wait until the system is in balance

5. If it continues to oscillate, repeat 3 and 4

If the time of oscillation is shorter than the integration time:

(T

p

 < T

n

 , (T

n

 is, say, 240 seconds)).

1. Reduce K

p

 by, say, 20% of the scale reading.

2. Wait until the system is in balance.

3. If it continues to oscillate, repeat 1 and 2.

Summary of Contents for EKC 312

Page 1: ...njection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value User manual Electronic superheat controller Type...

Page 2: ...ve regulation of the refrigerant injection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value Functions y y...

Page 3: ...on is stopped when the connection is interrupted The function must be used when the compressor is stopped The controller then closes the solenoid valve so that the evaporator is not charged with refri...

Page 4: ...umption Controller ETS step motor 5 V A 1 3 V A Input signal Press transmitter 4 20 mA from AKS 33 Digital input from external contact func tion Sensor input 2 pcs Pt1000 ohm Alarm relay 1 pcs SPST AC...

Page 5: ...ification factor Kp If the Kp value is reduced the regulation becomes slower n04 Kp factor I Integration time Tn If the Tn value is increased the regulation becomes slower n05 Tn sec Max value for the...

Page 6: ...e if 2 has been selected Temperature reference if 3 has been selected o17 Display mode Manual control of outputs For service purposes the individual relay outputs and the ETS output can be forced Howe...

Page 7: ...Te Read the temperature at the S4 sensor u27 S4 temp Read value of current signal from pressure transmitter AIB u29 AI B mA DO1 Alarm Read status of alarm relay For Danfoss only Start up time for safe...

Page 8: ...ve s actual opening degree give the lower button a brief push 1s Define view in o17 Reference Units 0 C bar 1 F psig r05 0 1 0 Start stop of refrigeration r12 OFF On 1 Regulating parameters P Amplific...

Page 9: ...tcircuited S2 sensor E17 Cut out S4 sensor E18 Shortcircuited S4 sensor E20 The input signal on terminals 14 15 is outside the range P0 signal A11 Alarm message No refrigerant has been selected A43 Ch...

Page 10: ...are no substitute for normal good engineering practice Danfoss wil not be responsible for any goods or plant components damaged as a result of the above defects It is the installer s responsibility t...

Page 11: ...the regulation 2 Follow the menu survey on page 6 and set the various para meters to the required values 3 Switch on the external switch and regulation will start 4 Follow the actual superheat on the...

Page 12: ...uide for extended operation RC8AC Here you can see how a data communication connection to ADAP KOOL Refrigeration control systems can be established If the distance between EKC 312 and the ETS valve e...

Reviews: