Danfoss EKC 312 User Manual Download Page 4

4  

 

 

 

DKRCC.PS.R1.A3.02 / 520H9752 

 

© Danfoss A/S (DCS-IMCGPD/sw), 2015-03

Manual 

Electronic superheat controller, type EKC 312

Data

Necessary connections

Terminals:

25-26  Supply voltage 24 V AC.

21-24  Supply to step motor

18-19  Pt1000 sensor at evaporator outlet (S2)

14-15  Pressure transmitter type AKS 33

1-2 

Switch function for start/stop of regulation. If a switch is 

not connected, terminals 1 and 2 must be shortcircuited.

Application dependent connections

Terminal:

18-20  Pt1000 sensor for measuring air temperature (S4)

12-13   Alarm relay

There is connection between 12 and 13 in alarm situa tions 

and when the controller is dead

3-4  

Data communication

 

Mount only, if a data communication module has been 

mounted.

It is important that the installation of the data communi-

cation cable be done correctly. Cf. separate literature No. 

RC8AC...

Connections

Supply voltage

24 V AC +/-15% 50/60 Hz, 10 V A
(the supply voltage is galvanically sepa-
rated from the input and output signals)

Power consumption

Controller
ETS  step motor

5 V A
1,3 V A

Input signal 

Press. transmitter 4-20 mA from AKS 33
Digital input from external contact func-
tion

Sensor input

2 pcs. Pt1000 ohm

Alarm relay

1 pcs. SPST

AC-1: 4 A (ohmic)
AC-15: 3 A (inductive)

Step motor output

Pulsating 100 mA

Data communication

Possible to connect a data 
communication module

Ambient 

temperature

-10 – 55 °C, During operation
-40 – 70 °C, During transport
20 – 80% Rh, not condensed
No shock influence/vibrations

Enclosure

IP 20

Weight

300 g

Mounting

DIN rail

Display

LED, 3 digits

Approvals

EU Low Voltage Directive and EMC 
demands re CE-marking complied with.
LVD-tested acc. to EN 60730-1 
and EN 60730-2-9
EMC-tested acc. to EN50081-1 
and EN 50082-2

Data communication

< --------------- max. 5 m  --------------->

Ordering

Type

Function

Code No.

EKC 312

Superheat controller

084B7250

EKA 173

Data communication module (accessories), 
(FTT 10 module)

084B7092

EKA 175

Data communication module (accessories), 
(RS 485 module)

084B8679

EKA 174

Data communication module (accessories), 
(RS 485 module) with galvanic separation

084B7124

Temperature sensor Pt 1000 ohm / Pressure transmitter type AKS 33: Kindly refer to catalogue 
RK0YG ETS valves: Kindly refer to data sheet RD1TA

Summary of Contents for EKC 312

Page 1: ...njection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value User manual Electronic superheat controller Type...

Page 2: ...ve regulation of the refrigerant injection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value Functions y y...

Page 3: ...on is stopped when the connection is interrupted The function must be used when the compressor is stopped The controller then closes the solenoid valve so that the evaporator is not charged with refri...

Page 4: ...umption Controller ETS step motor 5 V A 1 3 V A Input signal Press transmitter 4 20 mA from AKS 33 Digital input from external contact func tion Sensor input 2 pcs Pt1000 ohm Alarm relay 1 pcs SPST AC...

Page 5: ...ification factor Kp If the Kp value is reduced the regulation becomes slower n04 Kp factor I Integration time Tn If the Tn value is increased the regulation becomes slower n05 Tn sec Max value for the...

Page 6: ...e if 2 has been selected Temperature reference if 3 has been selected o17 Display mode Manual control of outputs For service purposes the individual relay outputs and the ETS output can be forced Howe...

Page 7: ...Te Read the temperature at the S4 sensor u27 S4 temp Read value of current signal from pressure transmitter AIB u29 AI B mA DO1 Alarm Read status of alarm relay For Danfoss only Start up time for safe...

Page 8: ...ve s actual opening degree give the lower button a brief push 1s Define view in o17 Reference Units 0 C bar 1 F psig r05 0 1 0 Start stop of refrigeration r12 OFF On 1 Regulating parameters P Amplific...

Page 9: ...tcircuited S2 sensor E17 Cut out S4 sensor E18 Shortcircuited S4 sensor E20 The input signal on terminals 14 15 is outside the range P0 signal A11 Alarm message No refrigerant has been selected A43 Ch...

Page 10: ...are no substitute for normal good engineering practice Danfoss wil not be responsible for any goods or plant components damaged as a result of the above defects It is the installer s responsibility t...

Page 11: ...the regulation 2 Follow the menu survey on page 6 and set the various para meters to the required values 3 Switch on the external switch and regulation will start 4 Follow the actual superheat on the...

Page 12: ...uide for extended operation RC8AC Here you can see how a data communication connection to ADAP KOOL Refrigeration control systems can be established If the distance between EKC 312 and the ETS valve e...

Reviews: