7.8
Distribution circuits
Distribution circuit 1 is available from factory. Distribution circuits 2-5 require an expansion module, separately sold as accessory.
Up to 5 distribution circuits can be active simultaneously.
Example of settings for distribution circuit 1:
1. Press
in the upper left corner of the Start screen
2. Press
3. Continue with to the menu page for Mix valves.
4. Press the text Mix valves.
5. Press text for desired distribution circuit.
The distribution circuit must first be enabled. See step 6.
6. Page 1:
Enable the distribution circuit.
Settings for max/min supply temperature.
NOTE! The distribution circuit settings can not exceed the values set in the main heat curve.
Confirm the settings with
7. Page 2:
Settings for supply temperature at different outdoor temperatures.
NOTE! The distribution circuit settings can not exceed the values set in the main heat curve.
The temperature can be adjusted in two ways:
▪
If the Curve indicator
40
is lit, press or to adjust the entire curve.
▪
Press and drag individual curve points:
▪
If the Curve indicator
40
is not lit individual points can be moved separately by pressing and to the desired temper-
ature.
Confirm the settings with
The Curve indicator has two modes that can be toggled by pressing the Curve indicator symbol.
40
When lit, the curve is adjusted as one unit.
40
When not lit, individual curve points can be moved separately.
Commissioning
DHP-M
Danfoss Heating Solutions
VIJSE302
33
Summary of Contents for DHP-M
Page 1: ...MAKING MODERN LIVING POSSIBLE Commissioning DHP M www heating danfoss com...
Page 36: ...Commissioning DHP M VIJSE302 Danfoss Heating Solutions 36...
Page 37: ...Commissioning DHP M Danfoss Heating Solutions VIJSE302 37...
Page 38: ...Commissioning DHP M VIJSE302 Danfoss Heating Solutions 38...
Page 39: ...Commissioning DHP M Danfoss Heating Solutions VIJSE302 39...