
Fuse table
Heat pump
Heat pump + Immersion Heater
Immersion Heater only
3 kW
6 kW
9 kW
3 kW
6 kW
9 kW
400V, 3N~
5 - 17 kW
16 A
20 A
25 A
32 A
6 A
10 A
16 A
400V, 3N~
3 - 12 kW
10 A
16 A
20 A
25 A
6 A
10 A
16 A
Positioning of the outdoor sensor
H
2/3 x H
Recommended location
Unsuitable location
▪
Position the outdoor sensor on the north or north west side of the
house.
▪
Make sure that the outdoor sensor is not placed in direct sun light.
▪
For taller buildings, the sensor should be positioned between the
second and third floors.
▪
The sensor location must not be completely protected from the
wind but not placed in a direct draft.
▪
The outdoor sensor must not be placed on reflective panel walls.
▪
The sensor must be positioned at least 1 m from openings in the
walls which may emit hot air.
▪
If the sensor cable is connected through a pipe, the pipe must be
sealed so that the sensor is not affected by outgoing air.
Commissioning
DHP-H Varius Pro+/DHP-L Varius Pro+
Danfoss Heating Solutions
VIJSG202
11