Installation and User Guide
DEVIreg™ Hotwater
FEC | Produced by Danfoss ©
15
Temperature time table:
Temperature of
disinfection [C°]
Disinfection time
55
2h 00 minutes
56
1h 20 minutes
57
1h 00 minutes
58
0h 50 minutes
59
0h 45minutes
60
0h 40 minutes
61
0h 35 minutes
62
0h 30minutes
63
0h 28 minutes
64
0h 27 minutes
65
0h 26minutes
Temperature of
disinfection [C°]
Disinfection time
66
0h 25 minutes
67
0h 25 minutes
68
0h 22 minutes
69
0h 21 minutes
70
0h 20 minutes
71
0h 18minutes
72
0h 14 minutes
73
0h 12 minutes
74
0h 10 minutes
75
0h 10 minutes
Alarms view
By pressing
button from
Main Screen
–
screen(-s) with
Alarm
appears .
If more than
1
Alarm
is happened – use naviga-
tion by going
. Pressing
button again
leads from
Alarm
to
Main Screen
. Having an
active alarm will activate alarm relay . Alarms will
be retained till reset has been performed .
Main menu
By pressing
from the
Main Screen
– screen
Main Menu
appears .
The menu system is navigated from
Main
Screen
by the following sequence:
The main menu is navigated by
and
.
Pressing the
the selected sub-menu will be
shown . Pressing
button you will be taken
back to the previous menu step .