Installation and User Guide
DEVIreg™ Hotwater
FEC | Produced by Danfoss ©
21
Appendix A. BMS and RS-485 interface
The controller has a built-in Modbus data transmission system and can be connected to
the BMS central unit .
A1. Communication settings
Default communication settings:
•
Serial address: 1 .
•
Serial baud rate (Transmission speed): 19200 .
•
Serial setting: 8N1 .
A2. RS-485 specifications
MCX hardware network specifications (wiring, topology, etc .) can be found in Danfoss document:
User manual. Meet any HVAC requirement with the reliability of MCX network.
This document provides general indications for the setup of RS-485 networks .
A3. Modbus parameters and variables
Modbus parameters and variables for
DEVIreg™ Hotwater
controller .
LABEL
DESCRIPTION
MIN
MAX.
VALUE/
TYPE
UNIT
RW
ADU
PARAMETERS & STATUS VARIABLES
SYS
Main Menu > System variables
S1
MaxH1_0dec
0
100
80
RW
3001
S2
MaxH1_1dec
0 .0
100 .0
80 .0
RW
3002
S3
MaxH2_0dec
0
100
80
RW
3003
S4
MaxH2_1dec
0 .0
100 .0
80 .0
RW
3004
S5
MaxH3_0dec
0
100
80
RW
3005
S6
MaxH3_1dec
0 .0
100 .0
80 .0
RW
3006
S7
MaxH4_0dec
0
100
80
RW
3007
S8
MaxH4_1dec
0 .0
100 .0
80 .0
RW
3008
S9
AlarmH1
0 .0
90 .0
90 .0
RW
3009
S10
AlarmH2
0 .0
90 .0
90 .0
RW
3010
S11
AlarmH3
0 .0
90 .0
90 .0
RW
3011
S12
AlarmH4
0 .0
90 .0
90 .0
RW
3012
S13
InitConfigured
0
1
0
RW
3013
S14
Dis_warn
0
1
0
RW
3014
StU