Illustration 4.2: Power Management - Connections
The ripple control receiver is connected as follows:
Input Terminal Strip
Function
Ripple Control Receiver Connector (K)
+S
12-30 VDC
K1
-S1
Relay input 1
+S
12-30 VDC
K2
-S2
Relay input 2
+S
12-30 VDC
K3
-S3
Relay input 3
+S
12-30 VDC
K4
-S4
Relay input 4
+S
12-30 VDC
K5
-S5
Not used
+S
12-30 VDC
K6
-S6
Not used
A2-
12-30 VDC
(0)4 .. 20 mA
A2+
Analogue input
A1-
12-30 VDC
(0)4 .. 20 mA
A1+
Analogue input
Table 4.1: Ripple Control Receiver - Connections
To avoid damage to any product of the CLX Series and the ripple control receiver,
the connection must only be made by an authorised and suitably trained electri-
cian.
Note:
Further information on how to configure grid management via the integrated web interface
can found in the CLX Series user manual in the download area at www.danfoss.com/solar.
As default no grid management settings have been configured in the CLX Home GM or CLX
Standard GM, remember to configure the inputs/Relays according to the requirements from the
DNO. The configuration is carried out via the integrated web interface of the CLX Home GM or
CLX Standard GM.