Danfoss AR05 Operation Instructions Manual Download Page 20

20

Reglermanual - VMGFF102

5.6 - Control point

The control point represents the water temperature that the 
unit must produce. The heat exchanger entering water 
temperature is controlled by default, but the heat exchanger 
leaving water temperature can also be controlled (requires a 
Service confi guration modifi cation).

Control point = active se reset

5.6.1 - Active setpoint

Two setpoints can be selected as active in cooling mode and 
two in heating mode. Usually, the second setpoint is used for 
unoccupied periods. 

Depending on the current operating type, the active setpoint 
can be selected:
• 

by choosing the item in the GENUNIT menu,

• 

via the user’s volt-free contacts,

• 

via network commands

• 

via the setpoint timer program (schedule 2).

The following tables summarise the possible selections 
depending on the control types (local, remote or network) 
and the following parameters:
• 

Setpoint select in local control: item LSP_SEL in the 
GENUNIT menu permits selection of the active set-point, 
if the unit is in local operating type.

• 

Heating/cooling operating mode.

• 

Setpoint selection contacts: setpoint selection contact 
status.

• 

Schedule 2 status: schedule for setpoint selection.

LOCAL OPERATING MODE

PARAMETER STATUS

Heating/cooling 
operating mode

Local setpoint 
selection

Time schedule 2 
status

Active setpoint

Cooling

sp 1

-

Cooling setpoint 1

Cooling

sp 2

-

Cooling setpoint 2

Cooling 

auto

occupied

Cooling setpoint 1

Cooling

auto

unoccupied

Cooling setpoint 2

Heating

sp1

-

Heating setpoint 1

Heating

sp 2 

-

Heating setpoint 2

Heating

auto

occupied

Heating setpoint 1

Heating

auto

unoccupied

Heating setpoint 2

REMOTE OPERATING MODE

PARAMETER STATUS

Heating/cooling 
operating mode

Setpoint selection 
contact

Active setpoint

Cooling 

sp 1 (open)

Cooling setpoint 1 

Cooling

sp 2 (closed)

Cooling setpoint 2

Heating

sp 1 (open)

Heating setpoint 1

Heating

sp 2 (closed)

Heating setpoint 2

5.6.2 - Reset

Reset means that the active setpoint is modifi ed so that less 
machine capacity is required (in cooling mode, the setpoint is 
increased, in heating mode it is decreased). This modifi ca-tion 
is in general a reaction to a drop in the load. For the Pro-
Dialog control system, the source of the reset can be 
confi gured in the HCCONFIG confi guration: it can be 
provided either by the outdoor temperature (that gives a 
measure of the load trends for the building) or by the return 
water temperature (heat exchanger delta T,  gives an average 
building load). 

In response to a drop in the outdoor temperature or to a 
drop in delta T, the cooling setpoint is normally reset 
upwards in order to optimise unit performance: 

In both cases the reset parameters, i.e. slope, source and 
maximum value, are confi gurable in the RESETCFG menu (see 
section 4.3.8). Reset is a linear function based on three 
parameters.
• 

A reference at which reset is zero (outdoor temperature or 
delta T - no reset value).

• 

A reference at which reset is maximum (outdoor 
temperature or delta T - full reset value).

• 

The maximum reset value.

Reset example in cooling mode based on the outside 

temperature

Legend

Maximum reset value

OAT or delta T for no reset

OAT or delta T for full reset

D Building 

Load

5.7 - Demand limit

The demand limit is used to restrict the unit power 
consumption. The Pro-Dialog control system allows limitation 
of the unit capacity, using user-controlled volt-free contacts. 

The unit capacity can never exceed the limit setpoint 
activated by these contacts. The limit setpoints can be 
modifi ed in the SETPOINT menu.

5.8 - Night mode

The night period is defi ned (see GENUNIT confi guration) by a 
start time and an end time that are the same for each day of 
the week. During the night period, the number of fans 
operating can be reduced, and the unit capacity may be 
limited.

Reset value

Outdoor temperature (OAT)

Heat exchanger delta T

% Building load

Summary of Contents for AR05

Page 1: ...AR05 Control Operation instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP...

Page 2: ...ics 6 4 3 Password screens 6 4 4 Menu screen characteristics 7 4 5 Data screen or con gurable parameter characteristics 7 4 6 Parameter modi cation 7 4 7 Operating mode screen 8 4 8 Menu tree structur...

Page 3: ...egulate the AR05 units These units have one or two refrigerant circuits Controls compressor start up to control the water loop the fans to optimise operation of each refrigerant circuit the defrost cy...

Page 4: ...sure the suction and discharge pressure in each circuit Thermistors The heat exchanger water sensors are installed in the enter ing and leaving side The outdoor temperature sensor is mounted under a m...

Page 5: ...pump 1 J2B CH 22 NRCP2 BASE Command water pump 2 J2B CH 23 NRCP2 BASE The change over between the two pumps is con gurable Alarm relay output J3 CH 24 30A 31A NRCP2 BASE Unit operation relay output J3...

Page 6: ...ction screen Password entry screen Parameter modi cation screen NOTE If the interface is not used for a long period it will go black The control is always active the operating mode remains unchanged T...

Page 7: ...arameters such as the water temperature setpoints MAINMENU TEMP Current path in the menu structure EWT 12 0 C List of items LWT 7 0 C Cursor position OAT 35 0 C CHWSTEMP 17 8 C SCT_A 57 0 C Leaving Wa...

Page 8: ...Select Machine Mode Description of the screen Local On List of the machine operating modes Local Schedule Cursor CCN Remote The Up and Down keys position the cursor on the selected operating mode Fou...

Page 9: ...DAY BRODCAST DATETIME CTRL_ID HOLIDY01S HOLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs O...

Page 10: ...LWT nnn n C Heat exchanger leaving water temperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n...

Page 11: ...tput B1 exv_a 0 100 EXV position circuit B HD_POS_B 0 100 Position variable fan speed controller B RV_B On O Four way refrigerant valve C_HEATER On O Heat exchanger and lower coil heater BOILER On O B...

Page 12: ...of start ups fan B1 hr_cpum1 nnnnn hours Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles c...

Page 13: ...rent alarm 1 alarm_2c nnnnn Current alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus a...

Page 14: ...me Summer time startmon 1 to 12 3 Month startdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday s...

Page 15: ...0 to 13 9 0 C Delta T for maximum reset cr_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature...

Page 16: ...Monday P2 period 2 7h00 18h00 Monday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not us...

Page 17: ...l be in occupied or unoccupied mode depending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTEN...

Page 18: ...ange over to heating mode Heating cooling control can be automatic or manual In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold valu...

Page 19: ...customer safety loop see chapter 3 6 It prevents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 He...

Page 20: ...Heating sp 1 open Heating setpoint 1 Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modi ed so that less machine capacity is required in cooling mode the se...

Page 21: ...rotection and in all cases cannot satisfy the heating load The outdoor temperature is below a con gured threshold see HCCONFIG con guration The unit demand limit is not active The user may con gure th...

Page 22: ...eturn to an autonomous operating mode until the fault is cleared If the master unit is halted due to an alarm the slave unit is authorised to start without prior conditions ATTENTION For heat pumps op...

Page 23: ...hen communication is re established Installation bus fault or defective slave board Depending on the con guration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with...

Page 24: ...ve 45 P 43 Heat exchanger temperature too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor p...

Page 25: ...VMGFF102...

Reviews: