Reglermanual - VMGFF102
4.9.5 - INPUTS menu
NAME
FORMAT
UNIT
DESCRIPTION
ONOFF_SW
Open/Close
-
Remote start/stop contact
HC_SW
Open/Close
-
Remote heating/cooling contact
on_ctrl
Off , On Cool, On Heat, On
Auto
-
Current control
SETP_SW
Open/Close
-
Remote setpoint contact
LIM_SW1
Open/Close
-
Remote demand limit contact 1
LIM_SW2
Open/Close
-
Remote demand limit contact 2
FLOW_SW
Open/Close
-
Water fl ow rate/customer safety loop contact
leak_1_v
nn.n
Volt
Leak detector value 1
leak_2_v
nn.n
Volt
Leak detector value 2
DSHTR_SW
Open/Close
-
Desuperheater user contact
4.9.6 - OUTPUTS menu
NAME
FORMAT
UNIT
DESCRIPTION
CP_A1
On/Off
-
Compressor output A1
CP_A2
On/Off
-
Compressor output A2
CP_A3
On/Off
-
Compressor output A3
fan_a1
0-2
-
Fan output A1
fan_a2
0-2
-
Fan output A2
exv_a
0-100
%
EXV position circuit A
HD_POS_A
0-100
%
Position variable fan speed controller A
RV_A
On/Off
-
Four-way refrigerant valve
CP_B1
On/Off
-
Compressor output B1
CP_B2
On/Off
-
Compressor output B2
fan_b1
0-2
-
Fan output B1
exv_a
0-100
%
EXV position circuit B
HD_POS_B
0-100
%
Position variable fan speed controller B
RV_B
On/Off
-
Four-way refrigerant valve
C_HEATER
On/Off
-
Heat exchanger and lower coil heater
BOILER
On/Off -
Boiler
output
EHS_STEP
0-4
-
Electric heater stages
ALARM
On/Off -
Alarm
relay
RUNNING
On/Off
-
Unit on relay
4.9.7 - PUMPSTAT menu
NAME
FORMAT
UNIT
DESCRIPTION
CPUMP_1
On/Off
-
Command pump 1
CPUMP_2
On/Off
-
Command pump 2
ROT_PUMP
Yes/No
-
Pump rotation
WATPRES1
±nnn.n
kPa
Water pressure sensor 1
WATPRES2
±nnn.n
kPa
Water pressure sensor 2
WP_CALIB
Yes/No
-
Water pressure sensor calibration?
Following a water pressure sensor error, WP_OFFST is deconfi gured (-99 kPa) to inform of
the need to calibrate the water loop. This calibration must be made while there is no water
fl ow in the machine
WP_OFFST
±nnn.n
kPa
Water pressure sensor calibration value
DP_FILTR
nnn.n
kPa
Filter pressure drop
WP_MIN
nnn.n
kPa
Minimum water pressure
WAT_FLOW
±nnn.n
g/s
Water fl ow rate
CAPPOWER
±nnn.n
kW
Unit capacity
w_dt_spt
nn.n
^C
Setpoint delta T
w_dp_spt
nn.n
kPa
Setpoint delta P
drvp_pwr
+nnn.n
kW
Pump capacity
drvp_i
+nnn.n
A
Pump current
drvp_ver
xxxxxxxx
-
Variable pump speed controller version