4.9 - Detailed menu description
ATTENTION: Depending on the unit characteristics, certain menu items are not used.
4.9.1 - GENUNIT menu
NAME
FORMAT
UNIT
DESCRIPTION
ctrl_typ
0/1/2
-
Local = 0. CCN = 1. Remote = 2
STATUS
Running/Off /Stopping/
Delay
-
Operating status
ALM
Normal/Partial/Shutdown
-
Alarm status
min_left
0-15
min
Start-up delay
HEATCOOL
Heat/Cool/Standby/Both
-
Heating/cooling status
LOCAL_HC
0/1/2
-
Heating/cooling selection via the main interface
HC_SEL
0/1/2
-
Heating/cooling selection via the CCN network
0 = cooling, 1 = heating, 2 = auto
LSP_SEL
0/1/2
-
Setpoint selection via the main interface
SP_SEL
0/1/2
-
Setpoint selection via the CCN network
0 = Auto 1 = Spt1 2 = Spt2
SP_OCC
Yes/No
-
Occupied setpoint active
CHIL_S_S
Enable/Disable
-
Unit start/stop via the CCN network
CHIL_OCC
Yes/No
-
Unit time schedule via the CCN network
CAP_T
nnn
%
Total unit capacity
CAPA_T
nnn
%
Capacity circuit A
CAPB_T
nnn
%
Capacity circuit B
DEM_LIM
nnn
%
Demand limit value
SP
±nnn.n
°C
Current setpoint
CTRL_PNT
±nnn.n
°C
Control point
EMSTOP
Enable/Emstop
-
CCN emergency stop
4.9.2 - TEMP menu
NAME
FORMAT
UNIT
DESCRIPTION
EWT
±nnn.n
°C
Heat exchanger entering water temperature
LWT
±nnn.n
°C
Heat exchanger leaving water temperature
OAT
±nnn.n
°C
Outside air temperature
CHWSTEMP
±nnn.n
°C
Common master/slave temperature
SCT_A
±nnn.n
°C
Saturated condensing temperature A
SST_A
±nnn.n
°C
Saturated suction temperature A
SCT_B
±nnn.n
°C
Saturated condensing temperature B
SST_B
±nnn.n
°C
Saturated suction temperature B
DEFRT_A
±nnn.n
°C
Defrost temperature A
DEFRT_2
±nnn.n
°C
Defrost temperature B or second coil
sgtc1
±nnn.n
°C
Suction gas temperature, coil 1, unit with three compressors
sgtc2
±nnn.n
°C
Suction gas temperature, coil 2, unit with three compressors
4.9.3 - PRESSURE menu
NAME
FORMAT
UNIT
DESCRIPTION
DP_A
±nnn.n
kPa
Discharge pressure A
SP_A
±nnn.n
kPa
Suction pressure A
DP_B
±nnn.n
kPa
Discharge pressure B
SP_B
±nnn.n
kPa
Suction pressure B
4.9.4 - SETPOINT menu
NAME
FORMAT
VALUE
UNIT
DESCRIPTION
csp1
- 29.7 to 20
7.0
°C
Cooling setpoint 1
csp2
- 29.7 to 20
7.0
°C
Cooling setpoint 2
hsp1
20 to 55
38.0
°C
Heating setpoint 1
hsp2
20 to 55
38.0
°C
Heating setpoint 2
hramp_sp
0.1 to 1.1
0.60
^C
Ramp loading
cauto_sp
3.9 to 50
24.0
°C
Cooling change-over setpoint
hauto_sp
0 to 46.1
18.0
°C
Heating change-over setpoint
lim_sp1
0 to 100
100
%
Limit setpoint 1
lim_sp2
0 to 100
100
%
Limit setpoint 2
lim_sp3
0 to 100
100
%
Limit setpoint 3
min_sct
26.7 to 55*
40
°C
Condensing setpoint for desuperheater option
* 50, if the unit includes a variable-speed fan