Data sheet 

Actuators for modulating control AME 110 NL, AME 120 NL

DIP Switch Setting

(for service purposes only)

The actuator has a function selection DIP switch 

under the removable cover.  

 

The switch provides the following functions:

•   SW1: 

 

U/I - Input signal type selector 

  If set to OFF position, voltage input is 

selected. If set to ON position, current input is 

selected.

•  SW 2: 

 

0/2 -  Input signal range selector 

  If set to OFF position, the input signal is in 

the range from 2-10 V (voltage input) or from 

4-20 mA (current input). If set to ON position, 

the input signal is in the range from 0-10 

V (voltage input) or from 0-20 mA (current 

input).

•  SW 3: 

 

D/I - Direct or inverse acting selector

 

  If set to OFF position, the actuator is direct 

acting (stem contracts as voltage increases). If 

the actuator is set to ON position, the actuator 

is inverse acting (stem extracts as voltage 

increases).

•  SW 4:

 

---/Seq - Normal or sequential mode 

selector

 

  If set to OFF position, the actuator is working 

in the range 0(2)-10 V or 0(4)-20 mA. If set 

to ON position, the actuator is working in 

sequential range; 0(2)-5(6) V or 

 

(0(4-0(12) mA) or (5(6)-10 V) or  

(10(12)-20 mA).

•  SW 5: 

 

0-5/5-10 V - Input signal range in 

sequential mode

  If set to OFF position, the actuator is working 

in the sequential range 0(2)

-5(6) V or  

0(4)-10(12) mA. If set to ON position, the 

actuator is working in the sequential range; 

5(6)-10 V or 10(12)-20 mA.

•  SW 6: 

 

LIN/LOG - Linear or equal percentage flow 

through valve selector

 

If set to ON position, the flow through the 

valve is equal percentage-wise equals the 

control signal. If set to OFF position, the valve 

position is linear acc. to the control signal.

•  SW 7:

  ---/ASTK - Anti-blocking function

  Exercises the valve to avoid blocking in 

periods when the heating/cooling is off.

  If set to ON position (ASTK), the valve motion 

is switched on. The actuator opens and closes 

the valve every 7 days.

  If set to OFF position (---), the function is 

disabled.

•  SW 8:  

 

Reset switch and reset button on PCB

  Changing this switch position will cause the 

actuator to go through a self stroking cycle.

 

 

Note: 

Reset switch 

 

and reset button on 

PCB 

 have the same function. The reset 

switch must be in OFF position to make 

reset 

button function active ( press it for 2 sec. ).

Remark: 

Factory setting: All switches (except switch 2 which is in ON position) are in OFF positions.