background image

2

VD.KH.C6.02

   © Danfoss 01/2014

SMT/SI

Data sheet 

Actuators for modulating control AME 110 NL, AME 120 NL

Technical data

Type

AME 110 NL

AME 120 NL

Power supply

V

24 AC; +20 to −15% *  

Power consumption

running

VA

2

standby

W

0,5

Frequency

Hz

50/60

Control input Y

V

0-10 (2-10) Ri = 110 kΩ

mA

0-20 (4-20) Ri = 500 Ω

Closing force

N

130

Stroke

mm

5

Speed

s/mm

24

12

Relative humidity

max. 80 %

Max. medium temperature 

°C

120

Ambient temperature

0 … 55

Storage and transport temperature

 –40 … 70

Protection class

III safety extra-low voltage

Grade of enclosure

IP 42

Weight

kg

0,3

 - marking in accordance with

 

  

standards

Low Voltage Directive 2006/95/EC: EN 60730-1, EN 60730-2-14

 

EMC Directive 2004/108/EEC: EN 61000-6-2, EN 61000-6-3

* 24V AC; +10% to −15% if produced before w18y2013  

Installation

Mechanical

The actuator should be mounted with the valve 

stem in either horizontal position or pointing 

upwards.

The actuator is fixed to the valve body by means 

of a mounting ring, which requires no tools for 

mounting. The ring should be tightened by hand.

Electrical

Important:

 

It is strongly recommended that the 

mechanical installation is completed before the 

electrical installation.

Auto sleep mode

1.   If actuator AME 110 NL is charged by 24 V 

supply voltage and if it is not installed on 

  AB-QM valve, it will stop in lower position and 

switch off all LED indicators after 5 minutes 

2.  

It is mandatory to drive the spindle of the 

actuator to upper position before it will be 

installed on AB-QM valve (please refer to 

manual override drawings)!

3.  Auto sleep mode switches back to learning 

mode by pressing RESET button or by cycling 

power supply

Each actuator is supplied with the connecting 

cable for the controller.

Reviews: