•   Connect the device to the power supply 

  (see the section "Electrical installation/ 

 connection".

•   Press   3 times.

•   Press   

•   Press   or   to select between SINGLE,  

  COAXIAL D14 and COAXIAL D22.  

 Choose 

SINGLE and press   to confirm. 

•   Press   to change the PROBE LENGTH. 

 Press   to change the position of the  

 cursor. 

 

 Press   to decrease the value or   to 

  increase the value. 

 Press   to confirm. 

•   Press   to change of SCALE 4 mA. 

 Press   to change the cursor position. 

 Press   to decrease the value or   to 

  increase the value. 
 Press   to confirm. 

•   Press   to change of SCALE 20 mA. 

 Press   to change the cursor position. 

 Press   to decrease the value or   to 

  increase the value. 
 Press   to confirm.

•   Wait for QUICK SETUP to complete    

  8-second timeout

•   Press   to confirm.

•   Press   or   to select either  

  STORE NO or STORE YES.  

 Press   to confirm. 

  Default screen appears:

  Quick Setup completed

  You have the possibility of checking 

  your settings by pressing   twice.

 Press          to return to 

  default screen.

Quick Setup (all values below are only examples)

Note: 

The signal converter can be programmed with or without mechanical process connector assembled.

  Default screen

•   Press   

•   Press   

•   Press   

  Enter password: 
 

                

•   Press 

•   Press 

•   Press 

•   Press   to decrease the value or   to 

  increase the value. 
 Press   to confirm.

•   Press   4 times to return to default  
 screen.

  Default screen appears:

  Force mA completed and disabled

How to force mA output (all values below are only examples)

AKS 4100

QUICK SETUP?

YES                         NO

AKS 4100

PROBETYPE
SINGLECABLE

AKS 4100

PROBE LENGTH
                                 05000 mm

AKS 4100

SCALE 4mA
                                 04946 mm

AKS 4100

SCALE 20mA
                                 00070 mm

AKS 4100

QUICK SETUP

COMPLETED IN 8

AKS 4100

1.0.0

QUICK SETUP

AKS 4100

1.0.0

STORE NO

AKS 4100

DISTANCE
                     5000 mm

AKS 4100

SINGLE CABLE 

5000 mm

(0%) 4 mA 

4877 mm

(100%) 20 mA 

120 mm

AKS 4100

DISTANCE
                     5000 mm

AKS 4100

1.0.0

QUICK SETUP

AKS 4100

2.0.0

SUPERVISOR

AKS 4100

2.0.0

___________

AKS 4100

2.1.0

INFORMATION

AKS 4100

2.2.0

TESTS

AKS 4100

2.2.1

SET OUTPUT

AKS 4100

SET OUTPUT

3.5 mA

AKS 4100

SET OUTPUT

8 mA

AKS 4100

DISTANCE
                     5000 mm

Summary of Contents for AKS 4100U

Page 1: ...mm in mm in mm in 52 2 05 78 3 07 102 4 02 Total length of guided blades after cutting mm in mm in mm in 45 1 77 70 2 76 92 3 62 Steel wire insertion length 12 mm 0 47 in 12 mm 0 47 in 12 mm 0 47 in...

Page 2: ...e adjustment of dielectric constant Ammonia HFC HCFC 800 5000 31 5 197 90 3 5 Values to be entered into HMI Quick Setup menu and recorded on the setting label Stick the setting label onto the Signal C...

Page 3: ...ss M84H0010_1 AKS 41 41U with a c supply to AKS 4100 4100U with d c supply AKS 41 41U AKS 4100 4100U AKS 41 41U AKS 4100 4100U AC AKS 41 41U DC AKS 4100 4100U AKS 41 AKS 4100 AKS 41 41U AKS 4100 4100U...

Page 4: ...brown white E g ICM ICAD valve Feedback position ICM ICAD ICM ICAD ICM ICAD AKS 4100 4100U connected to PLC AKS 4100 4100U PLC PLC AKS 4100 4100U AKS 4100 PLC AKS4100 4100U Active Analog Input 4 20 mA...

Page 5: ...s set to DISTANCE the displayed value will be the distance from the Reference point to the top surface of the liquid refrigerant see fig 5 LEVEL is display option If the display is set to LEVEL then t...

Page 6: ...C0 F3 ML 520H8392 6 4 20 mA 1 2 3 Danfoss 4 5 Danfos 5 LEVEL LEVEL 5 OUTPUT 4mA 0 20mA 100 5 OUTPUTI mA mA 4 20m A 4mA 4 mA 20mA 20 mA 5 AKS 4100 4 20 1 2 3 Danfoss 4 5 5 5 4 0 20 100 5 4 20 4 0 20 10...

Page 7: ...a starting point for all measuring to determine Where to cut the cable Probe length see fig 5 Scale 4 mA see fig 5 Scale 20 mA see fig 5 Note the probe length Scale 4 mA and Scale 20 mA for use later...

Page 8: ...cking your settings by pressing twice Press to return to default screen Quick Setup all values below are only examples Note The signal converter can be programmed with or without mechanical process co...

Page 9: ...8 50 118 122 1 13 R717 NH3 Temperature range 60 50 C 76 122 F Temperature C Temperature F Dielectric constant of refrigerant gas Parameter 2 5 3 GAS EPS R 56 0 42 0 69 43 1 01 41 0 28 0 42 18 1 02 27...

Page 10: ...EPS R 60 48 76 54 1 01 47 36 53 32 1 02 35 28 31 18 1 03 27 21 17 6 1 04 20 15 17 5 1 05 14 10 4 14 1 06 9 6 13 22 1 07 5 2 23 29 1 08 1 2 30 36 1 09 3 5 37 41 1 10 6 8 42 47 1 11 9 11 48 52 1 12 12...

Page 11: ...I 5 m 197 in 2 mm 0 08 in 3 mm 2a 0 5 DN100 DN50 2a 1 2 3 6 2 3 6 0 mm 50 mm 2 2 3 6 AKS 4100 4100U 0 4 mA 100 20 mA 2 2b 5 mm 2c 3 4 5 4 mA 5 20 mA 5 4 mA 20 mA AKS 4100 4100U HMI 4 5 1 2 20 mm 0 8 i...

Page 12: ...AKS 4100 AKS 4100 05000 mm AKS 4100 4mA 04946 mm AKS 4100 20mA 00070 mm AKS 4100 8 AKS 4100 1 0 0 AKS 4100 1 0 0 NO AKS 4100 5000 mm AKS 4100 5000 mm 0 4 mA 4877 mm 100 20 mA 120 mm AKS 4100 2 2 0 AK...

Page 13: ...0 1 06 22 26 71 79 1 07 27 31 80 88 1 08 32 35 89 95 1 09 36 39 96 102 1 10 40 42 103 108 1 11 43 45 109 113 1 12 46 48 114 118 1 13 2 5 3 GAS EPS R 56 0 42 0 69 43 1 01 41 0 28 0 42 18 1 02 27 0 17 0...

Page 14: ...7 21 17 6 1 04 20 15 17 5 1 05 14 10 4 14 1 06 9 6 13 22 1 07 5 2 23 29 1 08 1 2 30 36 1 09 3 5 37 41 1 10 6 8 42 47 1 11 9 11 48 52 1 12 12 13 53 56 1 13 14 15 57 59 1 14 2 5 3 GAS EPS R 60 47 76 52...

Page 15: ...mm 0 08 AKS 4100 G1 AKS 4100U NPT 5 mm 6 1 HMI 5 m 197 2 mm 0 08 3 mm 2a x 0 5 DN100 DN50 2a 1 2 3 6 2 3 6 0 mm 50 mm 2a 2 3 6 AKS 4100 4100U 0 4mA 100 20mA 2 2b 5 mm 2c 3 4 5 4 mA 5 20 mA 5 AKS 4100...

Page 16: ...AKS 4100 4mA 04946 mm AKS 4100 20mA 00070 mm AKS 4100 8 AKS 4100 1 0 0 AKS 4100 1 0 0 AKS 4100 5000 mm AKS 4100 5000 mm 0 4 mA 4877 mm 100 20 mA 120 mm AKS 4100 5000 mm AKS 4100 1 0 0 AKS 4100 2 0 0...

Page 17: ...5 C 69 59 F C F 2 5 3 GAS EPS R 60 50 76 58 1 00 49 25 57 13 1 01 24 10 12 14 1 02 9 0 15 32 1 03 1 8 33 46 1 04 9 15 47 59 1 05 16 21 60 70 1 06 22 26 71 79 1 07 27 31 80 88 1 08 32 35 89 95 1 09 36...

Page 18: ...18 13 1 9 1 05 12 8 10 18 1 06 7 4 19 25 1 07 3 0 26 32 1 08 1 4 33 40 1 09 5 7 41 45 1 10 8 10 46 50 1 11 11 12 51 54 1 12 13 15 55 59 1 13 R410A 65 15 C 85 59 F C F 2 5 3 GAS EPS R 60 48 76 54 1 01...

Page 19: ...80 C 40 175 F HMI 20 60 C 4 140 F 1 100 14 5 2 1450 2 5 197 2 0 08 AKS 4100 G 1 AKS 4100U NPT 5 6 1 HMI 5 5 197 2 0 08 3 2a 0 5 100 50 2a 1 2 3 6 0 50 2a 2 3 6 4 0 20 100 2 2b 5 2c 3 4 5 4 5 20 5 20 4...

Page 20: ...S 4100 05000 mm AKS 4100 4 04946 mm AKS 4100 20 00070 mm AKS 4100 8 AKS 4100 1 0 0 AKS 4100 1 0 0 AKS 4100 5000 mm AKS 4100 5000 mm 0 4 mA 4877 mm 100 20 mA 120 mm AKS 4100 5000 mm AKS 4100 1 0 0 AKS...

Page 21: ...15 C 69 59 F C F 2 5 3 GAS EPS R 60 50 76 58 1 00 49 25 57 13 1 01 24 10 12 14 1 02 9 0 15 32 1 03 1 8 33 46 1 04 9 15 47 59 1 05 16 21 60 70 1 06 22 26 71 79 1 07 27 31 80 88 1 08 32 35 89 95 1 09 3...

Page 22: ...8 10 18 1 06 7 4 19 25 1 07 3 0 26 32 1 08 1 4 33 40 1 09 5 7 41 45 1 10 8 10 46 50 1 11 11 12 51 54 1 12 13 15 55 59 1 13 R410A 65 15 C 85 59 F C F Dielectric constant of refrigerant gas Parameter 2...

Page 23: ...Danfoss DCS MWA 2017 07 DKRCI PI SC0 F3 ML 520H8392 23...

Page 24: ...Danfoss DCS MWA 2017 07 DKRCI PI SC0 F3 ML 520H8392 24...

Reviews: