background image

© Danfoss | DCS (MWA) | 2017.07

DKRCI.PI.SC0.F3.ML | 520H8392 | 7

ENGLISH

Please observe that AKS 4100/4100U  

is intended to always be installed in  

a standpipe (column / bypass / stilling  

well). A Standpipe is commonly used when:

•  Servicing the AKS 4100

•  There is highly conductive foam in the tank.

•  The liquid is very turbulent or agitated.

Refrigerants

AKS 4100/4100U is designed specifically to measure 

liquid level in the most commonly used refrigerants, 

including R717(ammonia), HCFC, HFC and non 

corrosive gases / liquids.
AKS 4100/4100U can also be used with R744 (CO

2

) in 

the coaxial version. Please see the technical 

brochure for further details.  

Basic data 

AKS 4100/4100U is a passive 2-wired 4 – 20 mA 

sensor that is loop powered.

Supply Voltage

14 – 30 V DC Min/Max. value for a max. output of 22 

mA at the terminal

Load

RL [Ω] ≤ ((Uext -14 V)/20 mA).  

– Default (Error output set to 3.6 mA)

RL [Ω] ≤ ((Uext -14 V)/22 mA).  

– (Error output set to 22 mA)

Cable gland

AKS 4100 

PG 13, M20×1.5 ;  

 

  (cable 

diameter: 

 

   

 

6-8 mm (0.24-0.31in.)

AKS 4100U 

½ in. NPT

Terminals (spring loaded)

0.5-1.5 mm

2

 (~20-15 AWG)

Enclosure

IP 67 (~NEMA type 4X)

Refrigerant temperature

-60 – 100 °C / -76 – 212 °F

Refrigerants

The listed refrigerants are qualified and approved by 

Danfoss:

R717 / NH

3

-40 – 50 °C / -40 – 122 °F

R744 / CO

2

-50 – 15 °C / -58 – 59 °F

HCFC:

R22:  

-50 – 48 °C / -58 – 118 °F

HFC:

R404A:  

-50 – 15 °C / -58 – 59 °F

R410A:  

-50 – 15 °C / -58 – 59 °F

R134A  

-40 – 50 °C / -40 – 122 °F

(Further details in the Technical Brochure)
Ambient temperature

-40 – 80 °C / -40 – 175 °F

For HMI : -20 – 60 °C / -4 – 140 °F 

Process pressure

-1 – 100 barg / -14.5 – 1450 psig
Mechanical process connection with 5 m / 197 in.  

Ø2 mm / 0.08 in. stainless cable:

AKS 4100 

G1 inch pipe thread.  

 

   

 

Aluminium gasket included

AKS 4100U 

¾ in. NPT

(Further details in the Technical Brochure)

Mechanical Installation

Preparations prior to Mechanical Installation

Disassemble the Signal Converter from the 

Mechanical process connection (use 5´mm hex key, 

see fig. 6). Fit the red protection cover on top of the 

Mechanical process connection to protect it againt 

any moisture or dirt paticles. 
Content supplied (fig. 1)

 

Signal Converter (with or without HMI)

 

Mechanical process connection with  

 

5 m / 197 in. Ø2 mm / 0.08 in. stainless wire

 

Counterweight

 

Accessory bag comprising: 

 

3 mm set screws. 

 

Red cover to protect mechanical process  

 connection 

 prior to mounting Signal  

 converter.

 

Setting label.

Note:

Stand pipe design guidelines:

The side connection pipes must NOT 

penetrate into the stand pipe (fig. 2a)

Recommended diameter of the side 

connection pipe: 0.5 x stand pipe diameter 

(e.g. if stand pipe has diameter DN100, the 

side connection must be diameter DN50 or 

smaller) (fig. 2a).

If above design guidelines for side connection are 

not fulfilled, one of the following options are 

recommended:
1.  Increase Detection Delay. Parameter 2.3.6. 

 

  We recommend to increase the Detection Delay  

  (parameter 2.3.6) from the standard  

  0 mm to a value  below the lowest point of the  

  top side connection plus 50 mm (fig. 2a).
  Changing the Detection Delay (parameter  

  2.3.6) does not require changing the (0% ) 4mA  

  and (100%)20mA settings in the AKS 4100/4100U

  Within the Detection Delay zone, no measuring  

  will take place.
2.   Exchange from Cable to Coaxial version.
The stand pipe must have the SAME diameter through 

out the entire length. If standpipe diameter differs in 

width (fig. 2b) the Cable version is not recommended. 

Coaxial version should be used.
Adjustment of the counterweight blades

Allow 5 mm space between the guided blades and 

the inner wall of the pipe (see fig. 2c). Use side 

cutters to trim the guided blades to fit the actual 

standpipe diameter (see fig. 3).
Adjustment of the cable probe

  

   

 Please observe that the stainless steel wire is 

not permanently creased or kinked. 

Always use the reference point, at the Mechanical 

Process Connection (see fig. 4), as a starting point 

for all measuring to determine: 

•   Where to cut the cable.

•   Probe length (see fig. 5)

•   Scale 4 mA (see fig. 5)

•   Scale 20 mA (see fig. 5)
Note the probe length, Scale 4 mA and Scale 20 mA 

for use later when programming the HMI (Human 

Machine Interface) on the AKS 4100/4100U.
Follow these instructions and see fig. 4 & 5:

1.  Measure the inner length of the Standpipe.
2.  

Preparation before cutting the cable

  Known data:

  Space below counterweight:  20 mm / 0.8 in.

  Steel wire insertion length in  

 

  counterweight: 12 mm / 0.5 in.

  counterweight height: 33 mm / 1.3 in.

  Max Probe length =

  Standpipe inner length 

–   Space below counterweight (20 mm / 0.8 in.)

  The cable length =

  Max probe length 

+  Steel wire insertion

  length in counterweight (12 mm / 0.5 in.)  

–   Counterweight height (33 mm / 1.3 in.)

3.  Measure out the cutting point of the cable.  

  Measure from the reference point (fig. 4)  

  and cut the cable.
4.  Fit the counterweight on the cable and  

  secure the two set screws with a 3 mm Allen  

 Key 

(fig. 3).

5.  Lower the counterweight down through    

  the threaded hole. Make sure that the  

 

  counterweight is gliding down through    

  the pipe without any resistance and  

  that the cable is straight (not touching    

  the inner walls of the stand pibe or any  

  incoming piping (see fig. 2a)). 
6.  Use a torque wrench to tighten the  

 

  mechanical process connection  

  (fig. 1, item 2) to 120 Nm (89 lb/ft).
Calculating the measuring range

4 mA 

setting for max. measuring range:

  =  Max probe length 

–   Counterweight height (33 mm / 1.3 in.)

–  Bottom dead zone (see fig. 5)

20 mA

 setting for max. measuring range:

= Top dead zone (see fig. 5) 

Example

Known data:

Space below counterweight:  20 mm / 0.8 in.

Steel wire insertion length in  

 

counterweight: 12 mm / 0.5 in.

counterweight height: 33 mm / 1.3 in.

Preconditions:

 

Factory setting is used

Refrigerant = Ammonia

Standpipe inner length = 3100 mm / 122 in.

Max probe length =  

3100 mm – 20 mm = 3080 mm

(122 in. – 0.8 in. = 121.3 in.)
The cable length:

  Max probe length =  

+  Steel wire insertion length in   

 

counterweight (12 mm / 0.5 in.)  

–   Counterweight height (33 mm / 1.3 in.)

  3080 mm + 12 mm – 33 mm = 3059 mm

 (121.3 in. + 0.5 in. – 1.3 in. = 120.4 in.)

4 mA

 Setting for Max. Measuring Range:

  Max probe length (3080 mm / 121.3 in.)

–  Counterweight height (33 mm / 1.3 in.)

–  Bottom dead zone (see fig. 5) 

  (210 mm / 8.3 in.) = 2837 mm / 111.7 in.

20 mA

 Setting for Max. Measuring Range:

= Top dead zone (see fig. 5) = 120 mm / 4.7 in. 

How to mount the AKS 4100/4100U Converter 

(see fig 6) 
1.  Unscrew the set and ventilation screws with a  

  5 mm Hexagon key in the Signal converter.
2.  Push the Signal Converter downwards to stop on  

  the Mechanical process connection
3.  Turn the Signal Converter to the wanted position.
4.  Screw the set screw with a 5 mm Hexagon key.
5.  Screw the ventilation screw with a 5 mm Hexagon  

 key.

Electrical installation/connection

Output terminals (fig. 7 and 8):

1.  Current output –

2.  Current

3.  Grounding terminal 
Electrical installation procedure  

1.   Use a 2.5 mm Allen wrench to loosen the cover 

stop.

2.   Remove the terminal compartment cover from 

the housing.

3.  Do not disconnect the wire from the  

  terminal compartment cover.    

 

Put the terminal compartment cover  

  adjacent to the housing.

4.  Connect the wires to the device.  

  Tighten the cable entry glands.

5.   Attach the terminal compartment cover to the 

housing.

6.   Use a 2.5 mm Allen wrench to tighten the cover 

stop.

Start up:

•   Connect the converter to the power supply.

•   Energize the converter.

Devices with the HMI display option only: After 10 

seconds the screen will display "Starting up". After 20 

seconds the screen will display the software version 

numbers. After 30 seconds the default screen (fig. 

12) will appear.
Precausions when changing from 

AKS 41/41U to AKS 4100/4100U
Note:

AKS 41/41U supports both AC and DC supply 

whereas the AKS 4100/4100U is using DC supply 

only. Follow the instructions in fig. 9.
Connecting to controller or PLC

Follow the instructions in fig. 10 or 11.

The current output will be set to 3.6 mA 

whenever the AKS 4100/4100 detects an 

error like Marker 1, 2 or 3 (see page 4).

Quick Setup 

Summary of Contents for AKS 4100U

Page 1: ...mm in mm in mm in 52 2 05 78 3 07 102 4 02 Total length of guided blades after cutting mm in mm in mm in 45 1 77 70 2 76 92 3 62 Steel wire insertion length 12 mm 0 47 in 12 mm 0 47 in 12 mm 0 47 in...

Page 2: ...e adjustment of dielectric constant Ammonia HFC HCFC 800 5000 31 5 197 90 3 5 Values to be entered into HMI Quick Setup menu and recorded on the setting label Stick the setting label onto the Signal C...

Page 3: ...ss M84H0010_1 AKS 41 41U with a c supply to AKS 4100 4100U with d c supply AKS 41 41U AKS 4100 4100U AKS 41 41U AKS 4100 4100U AC AKS 41 41U DC AKS 4100 4100U AKS 41 AKS 4100 AKS 41 41U AKS 4100 4100U...

Page 4: ...brown white E g ICM ICAD valve Feedback position ICM ICAD ICM ICAD ICM ICAD AKS 4100 4100U connected to PLC AKS 4100 4100U PLC PLC AKS 4100 4100U AKS 4100 PLC AKS4100 4100U Active Analog Input 4 20 mA...

Page 5: ...s set to DISTANCE the displayed value will be the distance from the Reference point to the top surface of the liquid refrigerant see fig 5 LEVEL is display option If the display is set to LEVEL then t...

Page 6: ...C0 F3 ML 520H8392 6 4 20 mA 1 2 3 Danfoss 4 5 Danfos 5 LEVEL LEVEL 5 OUTPUT 4mA 0 20mA 100 5 OUTPUTI mA mA 4 20m A 4mA 4 mA 20mA 20 mA 5 AKS 4100 4 20 1 2 3 Danfoss 4 5 5 5 4 0 20 100 5 4 20 4 0 20 10...

Page 7: ...a starting point for all measuring to determine Where to cut the cable Probe length see fig 5 Scale 4 mA see fig 5 Scale 20 mA see fig 5 Note the probe length Scale 4 mA and Scale 20 mA for use later...

Page 8: ...cking your settings by pressing twice Press to return to default screen Quick Setup all values below are only examples Note The signal converter can be programmed with or without mechanical process co...

Page 9: ...8 50 118 122 1 13 R717 NH3 Temperature range 60 50 C 76 122 F Temperature C Temperature F Dielectric constant of refrigerant gas Parameter 2 5 3 GAS EPS R 56 0 42 0 69 43 1 01 41 0 28 0 42 18 1 02 27...

Page 10: ...EPS R 60 48 76 54 1 01 47 36 53 32 1 02 35 28 31 18 1 03 27 21 17 6 1 04 20 15 17 5 1 05 14 10 4 14 1 06 9 6 13 22 1 07 5 2 23 29 1 08 1 2 30 36 1 09 3 5 37 41 1 10 6 8 42 47 1 11 9 11 48 52 1 12 12...

Page 11: ...I 5 m 197 in 2 mm 0 08 in 3 mm 2a 0 5 DN100 DN50 2a 1 2 3 6 2 3 6 0 mm 50 mm 2 2 3 6 AKS 4100 4100U 0 4 mA 100 20 mA 2 2b 5 mm 2c 3 4 5 4 mA 5 20 mA 5 4 mA 20 mA AKS 4100 4100U HMI 4 5 1 2 20 mm 0 8 i...

Page 12: ...AKS 4100 AKS 4100 05000 mm AKS 4100 4mA 04946 mm AKS 4100 20mA 00070 mm AKS 4100 8 AKS 4100 1 0 0 AKS 4100 1 0 0 NO AKS 4100 5000 mm AKS 4100 5000 mm 0 4 mA 4877 mm 100 20 mA 120 mm AKS 4100 2 2 0 AK...

Page 13: ...0 1 06 22 26 71 79 1 07 27 31 80 88 1 08 32 35 89 95 1 09 36 39 96 102 1 10 40 42 103 108 1 11 43 45 109 113 1 12 46 48 114 118 1 13 2 5 3 GAS EPS R 56 0 42 0 69 43 1 01 41 0 28 0 42 18 1 02 27 0 17 0...

Page 14: ...7 21 17 6 1 04 20 15 17 5 1 05 14 10 4 14 1 06 9 6 13 22 1 07 5 2 23 29 1 08 1 2 30 36 1 09 3 5 37 41 1 10 6 8 42 47 1 11 9 11 48 52 1 12 12 13 53 56 1 13 14 15 57 59 1 14 2 5 3 GAS EPS R 60 47 76 52...

Page 15: ...mm 0 08 AKS 4100 G1 AKS 4100U NPT 5 mm 6 1 HMI 5 m 197 2 mm 0 08 3 mm 2a x 0 5 DN100 DN50 2a 1 2 3 6 2 3 6 0 mm 50 mm 2a 2 3 6 AKS 4100 4100U 0 4mA 100 20mA 2 2b 5 mm 2c 3 4 5 4 mA 5 20 mA 5 AKS 4100...

Page 16: ...AKS 4100 4mA 04946 mm AKS 4100 20mA 00070 mm AKS 4100 8 AKS 4100 1 0 0 AKS 4100 1 0 0 AKS 4100 5000 mm AKS 4100 5000 mm 0 4 mA 4877 mm 100 20 mA 120 mm AKS 4100 5000 mm AKS 4100 1 0 0 AKS 4100 2 0 0...

Page 17: ...5 C 69 59 F C F 2 5 3 GAS EPS R 60 50 76 58 1 00 49 25 57 13 1 01 24 10 12 14 1 02 9 0 15 32 1 03 1 8 33 46 1 04 9 15 47 59 1 05 16 21 60 70 1 06 22 26 71 79 1 07 27 31 80 88 1 08 32 35 89 95 1 09 36...

Page 18: ...18 13 1 9 1 05 12 8 10 18 1 06 7 4 19 25 1 07 3 0 26 32 1 08 1 4 33 40 1 09 5 7 41 45 1 10 8 10 46 50 1 11 11 12 51 54 1 12 13 15 55 59 1 13 R410A 65 15 C 85 59 F C F 2 5 3 GAS EPS R 60 48 76 54 1 01...

Page 19: ...80 C 40 175 F HMI 20 60 C 4 140 F 1 100 14 5 2 1450 2 5 197 2 0 08 AKS 4100 G 1 AKS 4100U NPT 5 6 1 HMI 5 5 197 2 0 08 3 2a 0 5 100 50 2a 1 2 3 6 0 50 2a 2 3 6 4 0 20 100 2 2b 5 2c 3 4 5 4 5 20 5 20 4...

Page 20: ...S 4100 05000 mm AKS 4100 4 04946 mm AKS 4100 20 00070 mm AKS 4100 8 AKS 4100 1 0 0 AKS 4100 1 0 0 AKS 4100 5000 mm AKS 4100 5000 mm 0 4 mA 4877 mm 100 20 mA 120 mm AKS 4100 5000 mm AKS 4100 1 0 0 AKS...

Page 21: ...15 C 69 59 F C F 2 5 3 GAS EPS R 60 50 76 58 1 00 49 25 57 13 1 01 24 10 12 14 1 02 9 0 15 32 1 03 1 8 33 46 1 04 9 15 47 59 1 05 16 21 60 70 1 06 22 26 71 79 1 07 27 31 80 88 1 08 32 35 89 95 1 09 3...

Page 22: ...8 10 18 1 06 7 4 19 25 1 07 3 0 26 32 1 08 1 4 33 40 1 09 5 7 41 45 1 10 8 10 46 50 1 11 11 12 51 54 1 12 13 15 55 59 1 13 R410A 65 15 C 85 59 F C F Dielectric constant of refrigerant gas Parameter 2...

Page 23: ...Danfoss DCS MWA 2017 07 DKRCI PI SC0 F3 ML 520H8392 23...

Page 24: ...Danfoss DCS MWA 2017 07 DKRCI PI SC0 F3 ML 520H8392 24...

Reviews: