2. Rescan the system: 

Having replaced the existing device with a new on the same address (084B4082 in this example), 

Rescan

 the system. 

Current 

Scan Status

 will now show the new detected device as ‘Uncfg’.

Navigating to 

Configuration 

 Control 

 Refrigeration 

 Circuits, ‘Mismatch’

 is shown next 

to the newly added device to indicate that a wrong configuration file is in use for the newly added 

device. Ensure the “Show only scanned Devices“ is set to  “Yes”.

3. Setup the new device correctly:

Note: the correct EDF file for the new device MUST be installed!

Change the configuration file to the correct one and confirm that the ‘Mismatch’ message is gone.

Operating Guide | AK-SM 800

© Danfoss | DCS (vt) | 2019.09

AQ314725020974en-000101 | 3