Overview

Reconfiguration step-by-step

Replacement process

When replacing a generic device on an AK-SM 800 system, issues are seen which leads to additional 

time spent during this replacement process.

Typical issues are:

1. Duplicate addresses
2. Uncfg messages shown
3. *Mismatch* shown
4. Loss of programmed settings

The following guideline explains how to address and/or avoid such issues by following a standard 

replacement method. The guide also describes known pitfalls which could lead to above issues.

It is the precondition for this guideline that a system is fully configured and operational with at least 

one case controller (generic device).

Replace controller

and connect device

Update SM 800 

Firmware

Install required EDF 

files and Device List

Reconfigure SM 

800 for new device

Step 1: Replace controller

Before making the physical replacement of 

the device, ensure that unintended alarms 

are not sent to monitoring centers. The field 

communication line must be disconnected and 

the new device reconfigured, before the alarm 

system will function properly again for the given 

device.

Replace the controller and reconnect the field 

communication line from the System Manager to 

the new device.

Configure the device with the correct field bus 

address and application.

Step 3: Install required EDF files 

and Device List

Please refer to the User Guide 

BC316842192932en-00010

All changes to the device.ls3 file and EDF files 

require a unit reset.

Step 2: Update SM 800 firmware

It is advised to always use the latest SM 800 

firmware in order to take advantage of features 

and support for latest devices.

Please refer to the User Guide 

BC316842192932en-000101

1. Confirm scan status:

Confirm current Scan Status for existing configuration. Address 10 shows an existing AK-CC 550 

MODBUS.

Step 4: Reconfigure SM 800 for new device

The recommended method to reconfiguring a 

newly added device as replacement of another 

is to use the manual configuration screens rather 

than the assisted layout wizard. 

If you are replacing the controller with a 

controller of the same type and software version, 

no EDF related changes to the system manager is 

required.