60
Capacity
controller RS8ER302 © Danfoss 2016-02
AK-CH
650
1. Go to Configuration menu
2. Select Thermostats
3. Define the required thermostat
function
Configuration - continued
Via the +- button you can move to similar set-
tings for the pressure control functions. (Not
used in the example)
In our example we select one termostat
function for monitoring the plant room
temperature.
We have subsequently entered a name for the
function.
3 - Thermostats
The general thermostats can be used to monitor
the temperature sensors that are used, as well
as 4 extra temperature sensors. Each thermostat
has a separate outlet to control external automa-
tion.
No. of thermostats
Set the number of general thermostats.
For each thermostat adjust
• Name
• Which of the sensors is used
Actual temp.
Temperature measurement on the sensor that is
attached to the thermostat
Actual state
Actual status on the thermostat outlet
Cut out temp.
Cut-out value for the thermostat
Cut in temp.
Cut-in value for the thermostat
High alarm limit
High alarm limit
Alarm delay high
Time delay for high alarm
Alarm text high
Indicate alarm text for the high alarm
Low alarm limit
Low alarm limit
Alarm delay low
Time delay for low alarm
Alarm text low
Indicate alarm text for low alarm
3b - Pressostats
There are similar settings for up to 3 pressure
switch functions.
Setup separate thermostat functions