Digital input signal - DI3 (high voltage input) 

The controller has a digital input 3 which can be used for one of the following functions:

Off: The input is not used.

1) Status display of 230 V signal

2) Door function. When the input is open it signals that the door is open. The refrigera-

tion and the fans are stopped. When the time setting in “A04” is passed, an alarm will be 

given.  and refrigeration resumed (o89). The refrigeration will be resumed when time in 

o89 has passed.

3) Door alarm. When the input is open it signals that the door is open. When the time set-

ting in “A04” is passed an alarm will be given.

4) Defrost. The function is started with a pulse signal.

5) Main switch. Regulation is carried out when the input is closed, and regulation is 

stopped when the input is put in pos. OFF.

6) Night operation. When the input is closed there will be regulation for night operation.

7) Thermostat band changeover. Switch to thermostat 2 (r21) when the input is closed.

8) Not used. 

9) Not used.

10) Case cleaning. The function is started with a pulse signal. See also description on page 

5.

11) Forced refrigeration used (at hotgas defrost) when the input is closed.

12) Night blinds. Pulse signal activates the night blinds.

13) Not used.

14) "Forced closing" when input is in pos. OFF.

15) Case Shutdown when input is closed.

o84

DI3 config.

Rail heat control

The rail heat can be controlled in several ways:

0: The function is not used

1: Pulse control is used with a timer function following the day/night operation (o41 and 

o42)

2: Pulse control is used with a dew point function. This function requires that a signal is 

received about the dew point value. The value is measured by a system manager and sent 

to the controller via the data communication.

o85

Railh. mode

Dew point value where the rail heat is minimum

This function is discussed earlier in the manual.

o86

DewP Min lim

Dew point value where the rail heat is maximum

This function is discussed earlier in the manual.

o87

DewP Max lim

Lowest permitted rail heat effect

Here the % part of the effect to be achieved when the dew point value is minimum.

o88

Rail Min ON%

Start of refrigeration when door is open

If the door has been left open, refrigeration must be started after a set time. That time can 

be set here. (DI config = 2)

o89

DoorInjStart

Fan for "Forced Closing"

You can set whether fans should be operational or stopped if the function "Forced closing" 

is activated here.

0: The fans will be stopped and defrosting will be permitted. 

1: The fans will run and defrosting will be permitted.

2: The fans will be stopped and defrosting will not be permitted. 

3: The fans will run and defrosting will not be permitted.

o90

ModeForcedCl

Alternative display

A reading can be displayed on the controller or on the display by pressing the lower 

button. This reading is set from the factory so that the defrosting stop temperature is 

displayed. 

A different setting will give the following reading:

1: (Defrost stop temperature = factory setting)

2: S6 temperature

3: S5B temperature (Application 6 and 8 only)

4: S3B temperature (Application 6, 7 and 8 only)

o92

Displ menu 2

Display of temperature during normal operation

1: Air temperature. Weighted S3 + S4

2: Product temperature S6

o97

Disp. Ctrl.

Light and night blind definition

0: Light is switched off and night blind is open when the main switch is off

1: Light and night blind is independent of main switch.

o98

Light MS = Off

Summary of Contents for AK-CC 450

Page 1: ...Controller for appliance control AK CC 450 User Guide...

Page 2: ...appliance The temperature of the evaporator is registered with the S5 sensor which can be used as a defrosting sensor In addition to the output for the solenoid valve the controller has 5 relay output...

Page 3: ...o refrigeration sections There are two defrost sensors one for each evaporator Application 6 Here the temperature and alarm monitoring are always controlled using the S4 sensor The two S3 temperatures...

Page 4: ...it can only be used in DX central plant or brine system In principle regulation in this system is the same as described above but is now performed with a PI function This results in reduced fluctuati...

Page 5: ...the appliance can also be used and which can register and monitor the temperature in the warmest part of the appliance There are separate alarm limits and time delays for the product sensor Appliance...

Page 6: ...he PMLX GPLX valve is closed completely before the hotgas is turned on Drip tray heating element It is possible to control a heating element in the drip tray for hot gas defrosting When defrosting is...

Page 7: ...a message to the system unit and then goes into a waiting position When every controller in the group is in a waiting position refrigeration is again permitted in all the individual controllers Defros...

Page 8: ...eration Here compressor 1 will start as the first one and when needed compressor 2 will be started Determined by thermostat band The compressor operating mode can be set in application 9 so that both...

Page 9: ...communication from a system unit Here there are two operational options if data communication should fail The light can go ON The light can stay in its current mode The light load must be connected t...

Page 10: ...defined for two different applications Alarm monitoring The controller monitors the door contact and delivers an alarm message if the door has been opened for a longer period than the set alarm delay...

Page 11: ...connected to the built in MODBUS the display can advantageously be changed to a type with screw terminals I e the type EKA 163A or EKA 164A If connection of two displays is required one must be conne...

Page 12: ...ration appliances or cold storage rooms In general all have outputs for Solenoid valve or compressor Fan Defrost Light In addition they have different uses and thereby input and outputs Application 1...

Page 13: ...nd two refrigeration sections The temperature is always controlled according to the S4 temperature There are two S3 sensors Alarm monitoring and display readings take place individually via the S3 sen...

Page 14: ...tory indicating application 1 If you employ another use labels are provided so that you can mount the relevant one For application 2 to 5 and 9 it is only the lower label that needs to be mounted For...

Page 15: ...in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the setting Correction of signal from S4 Compensation possibility due to long sensor cable r09 Adjust S4 Correction of signal from S3 Compensa...

Page 16: ...des LED will flash on the controller front panel and the alarm relay will cut in With data communication the impor tance of the individual alarms can be defined Setting is carried out in the Alarm des...

Page 17: ...hen defrosts start Min ON time in minutes c01 Min On time Min OFF time in minutes c02 Min Off time Time delay for couplings of two compressors Settings indicate the time that has to elapse from the fi...

Page 18: ...only relevant if you have chosen defrost with interval start d03 The function delays the interval time d03 by the set number of minutes but it only does it once and this at the very first defrost tak...

Page 19: ...Tn sec Fan Fan control Fan stop temperature The function stops the fans in an error situation so that they will not provide power to the appliance If the defrost sensor registers a higher temperature...

Page 20: ...input is closed 12 Night blinds Pulse signal activates the night blinds 13 14 Not used 15 Case Shutdown when input is closed o02 DI 1 Config Definition takes place with the numerical value shown to t...

Page 21: ...en the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but if there are any 15 minute network errors the light will switch on and the night blind...

Page 22: ...on This function requires that a signal is received about the dew point value The value is measured by a system manager and sent to the controller via the data communication o85 Railh mode Dew point v...

Page 23: ...mperature Weighted S3 S4 u56 Display air Measured temperature for alarm thermostat u57 Alarm air Status on relay for cooling u58 Comp1 LLSV Status on relay for fan u59 Fan relay Status on relay for de...

Page 24: ...s operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped for at least x minutes S3 3 The evaporator drips off and waits for the time to run out S4 4 Re...

Page 25: ...frost 16 A13 High temp S6 Temperature alarm High S6 1 A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigera...

Page 26: ...found in a rolling stack Push the uppermost or lowermost button to scan the rolling stack Set temperature 1 Push the middle button until the temperature value is shown 2 Push the upper or the lower bu...

Page 27: ...thermostat S4 r15 100 0 Alarm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for alarm funct S4 A36 0 100 0 Interval between defrost d03 6 h 6h 1...

Page 28: ...1 0 100 100 Heat function Neutral zone between refrigeration and heat function r62 1 0 K 50 K 2 Time delay at switch between refrigeration and heat function r63 1 1 0 min 240 min 0 Differential for th...

Page 29: ...at PWM n63 1 1 1 1 1 1 1 1 1 30 sec 900 sec 300 Max opening degree at PWM n64 1 1 1 1 1 1 1 1 1 0 100 100 Min opening degree at PWM n65 1 1 1 1 1 1 1 1 1 0 90 0 Expert setting Windup at PWM n66 1 1 1...

Page 30: ...election of EL diagram See overview page 12 and 13 o61 1 1 1 1 1 1 1 1 1 1 8 1 Download a set of predetermined settings See overview page 27 o62 1 1 1 1 1 1 1 1 1 0 6 0 Access code 2 partial access o6...

Page 31: ...u18 1 1 1 1 1 1 1 1 1 Temperature measured with S6 sensor product temperature u36 1 1 1 1 1 1 1 1 1 Status on DI2 output on 1 closed u37 1 1 1 1 1 1 1 1 1 Air temperature Weighted S3 S4 u56 1 1 1 1 1...

Page 32: ...gateway must be version 6 20 or higher RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal...

Page 33: ...ight must be on DI3 Digital input signal The signal must have a voltage of 0 230 V AC The function is defined in o84 Data communication If data communication is used it is important that the installat...

Page 34: ...Leak 1 mA Max 1 pcs coil Relays CE 250 V a c DO3 DO4 4 3 A DO2 DO5 DO6 4 3 A Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations...

Page 35: ...B8591 EKA 163B External display with plug for direct connection 084B8574 EKA 164B External display with operation buttons and plug for direct connections 084B8575 EKA 163A External display with screw...

Page 36: ...This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this materi...

Reviews: