 Controller for appliance control, AK-CC 450

© Danfoss | ADAP-KOOL® | 2015.10  

18 | RS8EU702 | 

Defrost method

Here you set whether defrost is to be accomplished with electricity, gas, brine or (none). 

During defrost the defrost relay will be cut in.

(With brine, the “cooling valve” will be kept open during the defrosting).

d01

Def. method

0 = none

1 = El

2 = Gas

3 = Brine

Defrost stop temperature

The defrost is stopped at a given temperature which is measured with a sensor (the sensor 

is defined in d10).

The temperature value is set.

d02

Def. Stop Temp

Interval between defrost starts

The function is zeroset and will start the timer function at each defrost start. When the 

time has expired the function will start a defrost.

The function is used as a simple defrost start, or it may be used as a safeguard if the normal 

signal fails to appear.

If master/slave defrost without clock function or without data communication is used, the 

interval time will be used as max. time between defrosts.

If a defrost start via data communication does not take place, the interval time will be used 

as max. time between defrosts.

When there is defrost with clock function or data communication, the interval time must 

be set for a somewhat longer period of time than the planned one, as the interval time will 

otherwise start a defrost which a little later will be followed by the planned one.

In connection with power failure the interval time will be maintained, and when the power 

returns the interval time will continue from the maintained value.

The interval time is not active when set to 0.

d03

Def Interval

(0=off)

Max. defrost duration

This setting is a safety time so that the defrost will be stopped if there has not already been 

a stop based on temperature or via coordinated defrost.

d04

Max Def. time

Time staggering for defrost cutins during start-up

The function is only relevant if you have several refrigeration appliances or groups where 

you want the defrost to be staggered in relation to one another. The function is further-

more only relevant if you have chosen defrost with interval start (d03).

The function delays the interval time d03 by the set number of minutes, but it only does 

it once, and this at the very first defrost taking place when voltage is connected to the 

controller.

The function will be active after each and every power failure.

d05

Time Stagg.

Drip-off time

Here you set the time that is to elapse from a defrost and until the compressor is to start 

again. (The time when water drips off the evaporator).

d06

DripOff time

Delay of fan start after defrost

Here you set the time that is to elapse from compressor start after a defrost and until the 

fan may start again. (The time when water is “tied” to the evaporator).

d07

FanStartDel

Fan start temperature

The fan may also be started a little earlier than mentioned under “Delay of fan start after 

defrost”, if the defrost sensor S5 registers a lower value than the one set here.

d08

FanStartTemp

Fan cut in during defrost

Here you can set whether fan is to operate during defrost.

0: Stopped (Runs during pump down)

1: Running (stopped during  "fan delay")

2: Running during pump down and defrost. After that stopped

d09

FanDuringDef

Defrost sensor 

Here you define the defrost sensor.

0: None, defrost is based on time

1: S5A

2: S4

3:  In  application 1 to 5 and 7: S5A + S6A

In application 6 and 8: Here is respectively stop on S5A and S5B.

d10

DefStopSens.

Pumpdown delay

Set the time where the evaporator is emptied of refrigerant prior to the defrost.

(In application 4, the relay DO1 is interrupted during pump down. In the other applica-

tions, the relay is closed).

d16

Pump dwn del.

Drain delay (only in connection with hotgas)

Set the time where the evaporator is emptied of condensed refrigerant after the defrost.

d17

Drain del

Defrost on demand – aggregate refrigeration time

Set here is the refrigeration time allowed without defrosts. If the time is passed, a defrost 

will be started.

With setting = 0 the function is cut out.

d18

MaxTherRunT

Delay on stop of heating in the drip tray

The time applies from the time the defrost stops by time or temperature to the time the 

heating element in the drip tray needs to be disconnected.

d20

Drip Tray del

Delay before opening hot gas valve

d23

HotGasInjDel

Summary of Contents for AK-CC 450

Page 1: ...Controller for appliance control AK CC 450 User Guide...

Page 2: ...appliance The temperature of the evaporator is registered with the S5 sensor which can be used as a defrosting sensor In addition to the output for the solenoid valve the controller has 5 relay output...

Page 3: ...o refrigeration sections There are two defrost sensors one for each evaporator Application 6 Here the temperature and alarm monitoring are always controlled using the S4 sensor The two S3 temperatures...

Page 4: ...it can only be used in DX central plant or brine system In principle regulation in this system is the same as described above but is now performed with a PI function This results in reduced fluctuati...

Page 5: ...the appliance can also be used and which can register and monitor the temperature in the warmest part of the appliance There are separate alarm limits and time delays for the product sensor Appliance...

Page 6: ...he PMLX GPLX valve is closed completely before the hotgas is turned on Drip tray heating element It is possible to control a heating element in the drip tray for hot gas defrosting When defrosting is...

Page 7: ...a message to the system unit and then goes into a waiting position When every controller in the group is in a waiting position refrigeration is again permitted in all the individual controllers Defros...

Page 8: ...eration Here compressor 1 will start as the first one and when needed compressor 2 will be started Determined by thermostat band The compressor operating mode can be set in application 9 so that both...

Page 9: ...communication from a system unit Here there are two operational options if data communication should fail The light can go ON The light can stay in its current mode The light load must be connected t...

Page 10: ...defined for two different applications Alarm monitoring The controller monitors the door contact and delivers an alarm message if the door has been opened for a longer period than the set alarm delay...

Page 11: ...connected to the built in MODBUS the display can advantageously be changed to a type with screw terminals I e the type EKA 163A or EKA 164A If connection of two displays is required one must be conne...

Page 12: ...ration appliances or cold storage rooms In general all have outputs for Solenoid valve or compressor Fan Defrost Light In addition they have different uses and thereby input and outputs Application 1...

Page 13: ...nd two refrigeration sections The temperature is always controlled according to the S4 temperature There are two S3 sensors Alarm monitoring and display readings take place individually via the S3 sen...

Page 14: ...tory indicating application 1 If you employ another use labels are provided so that you can mount the relevant one For application 2 to 5 and 9 it is only the lower label that needs to be mounted For...

Page 15: ...in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the setting Correction of signal from S4 Compensation possibility due to long sensor cable r09 Adjust S4 Correction of signal from S3 Compensa...

Page 16: ...des LED will flash on the controller front panel and the alarm relay will cut in With data communication the impor tance of the individual alarms can be defined Setting is carried out in the Alarm des...

Page 17: ...hen defrosts start Min ON time in minutes c01 Min On time Min OFF time in minutes c02 Min Off time Time delay for couplings of two compressors Settings indicate the time that has to elapse from the fi...

Page 18: ...only relevant if you have chosen defrost with interval start d03 The function delays the interval time d03 by the set number of minutes but it only does it once and this at the very first defrost tak...

Page 19: ...Tn sec Fan Fan control Fan stop temperature The function stops the fans in an error situation so that they will not provide power to the appliance If the defrost sensor registers a higher temperature...

Page 20: ...input is closed 12 Night blinds Pulse signal activates the night blinds 13 14 Not used 15 Case Shutdown when input is closed o02 DI 1 Config Definition takes place with the numerical value shown to t...

Page 21: ...en the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but if there are any 15 minute network errors the light will switch on and the night blind...

Page 22: ...on This function requires that a signal is received about the dew point value The value is measured by a system manager and sent to the controller via the data communication o85 Railh mode Dew point v...

Page 23: ...mperature Weighted S3 S4 u56 Display air Measured temperature for alarm thermostat u57 Alarm air Status on relay for cooling u58 Comp1 LLSV Status on relay for fan u59 Fan relay Status on relay for de...

Page 24: ...s operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped for at least x minutes S3 3 The evaporator drips off and waits for the time to run out S4 4 Re...

Page 25: ...frost 16 A13 High temp S6 Temperature alarm High S6 1 A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigera...

Page 26: ...found in a rolling stack Push the uppermost or lowermost button to scan the rolling stack Set temperature 1 Push the middle button until the temperature value is shown 2 Push the upper or the lower bu...

Page 27: ...thermostat S4 r15 100 0 Alarm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for alarm funct S4 A36 0 100 0 Interval between defrost d03 6 h 6h 1...

Page 28: ...1 0 100 100 Heat function Neutral zone between refrigeration and heat function r62 1 0 K 50 K 2 Time delay at switch between refrigeration and heat function r63 1 1 0 min 240 min 0 Differential for th...

Page 29: ...at PWM n63 1 1 1 1 1 1 1 1 1 30 sec 900 sec 300 Max opening degree at PWM n64 1 1 1 1 1 1 1 1 1 0 100 100 Min opening degree at PWM n65 1 1 1 1 1 1 1 1 1 0 90 0 Expert setting Windup at PWM n66 1 1 1...

Page 30: ...election of EL diagram See overview page 12 and 13 o61 1 1 1 1 1 1 1 1 1 1 8 1 Download a set of predetermined settings See overview page 27 o62 1 1 1 1 1 1 1 1 1 0 6 0 Access code 2 partial access o6...

Page 31: ...u18 1 1 1 1 1 1 1 1 1 Temperature measured with S6 sensor product temperature u36 1 1 1 1 1 1 1 1 1 Status on DI2 output on 1 closed u37 1 1 1 1 1 1 1 1 1 Air temperature Weighted S3 S4 u56 1 1 1 1 1...

Page 32: ...gateway must be version 6 20 or higher RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal...

Page 33: ...ight must be on DI3 Digital input signal The signal must have a voltage of 0 230 V AC The function is defined in o84 Data communication If data communication is used it is important that the installat...

Page 34: ...Leak 1 mA Max 1 pcs coil Relays CE 250 V a c DO3 DO4 4 3 A DO2 DO5 DO6 4 3 A Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations...

Page 35: ...B8591 EKA 163B External display with plug for direct connection 084B8574 EKA 164B External display with operation buttons and plug for direct connections 084B8575 EKA 163A External display with screw...

Page 36: ...This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this materi...

Reviews: