13-11 Comparator Operator
Array [6]
Option:
Function:
[0] *
<
Select < [0] for the result of the evaluation to be TRUE, when the variable selected in par.
13-10
is smaller than the fixed value in par.13-12
. The result
will be FALSE, if the variable selected in par.13-10
is greater than the fixed
value in par.13-12
.
[1]
≈
(equal)
Select
≈
[1] for the result of the evaluation to be TRUE, when the variable selected in par.
is approximately equal to the fixed value in par.13-12
[2]
>
Select > [2] for the inverse logic of option < [0].
13-12 Comparator Value
Array [6]
Range:
Function:
0 N/A*
[-100000.000 - 100000.000 N/A]
Enter the ‘trigger level’ for the variable that is monitored by this comparator. This is an array pa-
rameter containing comparator values 0 to 5.
3.10.4 13-2* Timers
This parameter group consists of timer parameters.
Use the result (TRUE or FALSE) from
timers
directly to define an
event
(see par.13-51
), or as boolean input in a
logic rule
(see par.
). A timer is only FALSE when started by an action (i.e.
Start timer 1 [29]) until the timer value entered in this parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array parameters with index 0 to 2. Select index 0 to program Timer 0, select index 1 to program Timer 1,
and so on.
13-20 SL Controller Timer
Array [8]
Range:
Function:
0 N/A*
[0 - 0 N/A]
Enter the value to define the duration of the FALSE output from the programmed timer. A timer is
only FALSE if it is started by an action (i.e.
Start timer 1
[29]) and until the given timer value has
elapsed.
3.10.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE / FALSE inputs) from timers, comparators, digital inputs, status bits and events using the logical operators
AND, OR, and NOT. Select boolean inputs for the calculation in par.13-40
. Define the operators used to logically combine the selected inputs in par.13-41
.
Priority of calculation
The results of par.13-40
are calculated first. The outcome
(TRUE / FALSE) of this calculation is combined with the settings of par.13-43
, yielding the final
result (TRUE / FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0] *
False
Enters the fixed value of FALSE in the logic rule.
[1]
True
Enters the fixed value TRUE in the logic rule.
[2]
Running
See parameter group 5-3* for further description.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
108
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3