[40]
Drive stopped
This logic rule is TRUE if the frequency converter is stopped or coasted by any means (either via
digital input, fieldbus or other).
[41]
Reset Trip
This logic rule is TRUE if the frequency converter is tripped (but not trip-locked) and the reset button
is pressed.
[42]
Auto Reset Trip
This logic rule is TRUE if the frequency converter is tripped (but not trip-locked) and an Automatic
Reset is issued.
[43]
OK Key
This logic rule is TRUE if the OK key on the LCP is pressed.
[44]
Reset Key
This logic rule is TRUE if the Reset key on the LCP is pressed.
[45]
Left Key
This logic rule is TRUE if the Left key on the LCP is pressed.
[46]
Right Key
This logic rule is TRUE if the Right key on the LCP is pressed.
[47]
Up Key
This logic rule is TRUE if the Up key on the LCP is pressed.
[48]
Down Key
This logic rule is TRUE if the Down key on the LCP is pressed.
[50]
Comparator 4
Use the result of comparator 4 in the logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the logic rule.
[70]
SL Time-out 3
Use the result of timer 3 in the logic rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic rule.
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
Select the first logical operator to use on the Boolean inputs from par.13-40
[13 -XX] signifies the boolean input of par. 13-*.
[0] *
DISABLED
Ignores par. , par.13-43
, and par.13-44
[1]
AND
Evaluates the expression [13-40] AND [13-42].
[2]
OR
evaluates the expression [13-40] OR[13-42].
[3]
AND NOT
evaluates the expression [13-40] AND NOT [13-42].
[4]
OR NOT
evaluates the expression [13-40] OR NOT [13-42].
[5]
NOT AND
evaluates the expression NOT [13-40] AND [13-42].
[6]
NOT OR
evaluates the expression NOT [13-40] OR [13-42].
[7]
NOT AND NOT
evaluates the expression NOT [13-40] AND NOT [13-42].
[8]
NOT OR NOT
evaluates the expression NOT [13-40] OR NOT [13-42].
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
110
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3