Connection, lower level 

Connection, upper level 

ENGLISH

Supply Voltage

The supply voltage is either 24 V or 110-230 V. See the label on 

the reverse side of the controller.

÷ = Plugs normally not used

However, if connecting to an external display, a jumper must 

be inserted between the connections "H" and "R".

Modbus

It is important that the installation of the data communication 

cable be done correctly. Cf. separate literature No. RC8AC.

Remember termination at the bus termination.

DO - Digital outputs, 8 pcs. DO1 - DO8

DO5 and DO6 are solid state relays. 

The relays are de-rated to the specified values.

If an alarm relay is defined, it will be driven under normal op-

eration and it will drop in the event of alarms and insufficient 

power to the controller. 

AO - Analogue output, 2 pcs. AO3 - AO4

Must be used when using a frequency converter or EC motors.

Connect 24 V on N and L (separate supply). Avoid earth fault 

current. Use double-insulated transformer. The secondary side 

must not be earthed.  

Obtain 0-10 volts from terminals N and AO3, respectively N and 

AO4. PAY ATTENTION TO THE POLARITY of N.

AI - Analogue inputs, 4 pcs. AI1 - AI4

Pressure transmitters

 

• Ratiometric: 10-90% of supply, AKS 32R

• Signal: 1-5 V, AKS 32

• Power: 0-20 mA / 4-20 mA, AKS 33 (supply = 12 V)

Temperature sensor

• Pt 1000 ohm, AKS 11 or AKS 21.

• NTC 86K ohm @ 25°C, from digital scroll.

Factory settings

AI1=PoA, AI2=PoB, AI3=Pc, AI4=Outdoor temperature SC3.

DI - Digital switch inputs, 8 pcs. DI1 - DI8

The connection may be a shut-down or interruption function. 

Select what is to be activated during configuration.

÷ = Plugs normally not used

AI - Analogue inputs, 4 pcs. AI5 - AI8

Pressure transmitters

 

• Ratiometric: 10-90% of supply, AKS 32R

• Signal: 1-5 V, AKS 32

Temperature sensor

• Pt 1000 ohm, AKS 11 or AKS 21.

• NTC 86K ohm @ 25°C, from digital scroll

DO

DO1

DO2

DO3

DO4

DO5

DO6

DO7

DO8

Σ 1-8

I Max. 10 A

(3,5)

10 A

(3,5)

6 A

(4)

6 A

(4)

0.5 A

min. 50 mA

Ioff < 1.5 mA

0.5 A

min. 50 mA

Ioff < 1.5 mA

6 A

(4)

6 A

(4)

32 A

U

All 24 V or all 230 V a.c.

Electric noise

Signal cables for sensors, DI inputs, data communication 

and display must be kept separate from high voltage 

(230 V) electric cables:

- Use separate cable trays

- Keep a distance between high voltage and signal cables 

of at least 10 cm

- Cables longer than 3 m at the DI input should be avoided

Separ

at

supply!

Warning

The supply voltage of AI may not share 

the signal with other controllers.

AKS 32

AKS 33

AKS 32R

10-90% ratiometric

1-5 V

0-20mA

4-20mA

Summary of Contents for ADAP-KOOL AK-PC 551

Page 1: ...0G0283 24 V a c d c 17 VA 080G0321 230 V a c 20 VA 080G0326 24 V a c d c 17 VA 080G0282 080G0321 080G0294 080G0075 230 V 080G0288 080G0326 080G0294 080G0075 24 V 1 5 m 080G0075 3 0 m 080G0076 MMIGRS2...

Page 2: ...f N AI Analogue inputs 4 pcs AI1 AI4 Pressure transmitters Ratiometric 10 90 of supply AKS 32R Signal 1 5 V AKS 32 Power 0 20 mA 4 20 mA AKS 33 supply 12 V Temperature sensor Pt 1000 ohm AKS 11 or AKS...

Page 3: ...lf This value can be increased if necessary Refrigeration No refrigeration The capacity from the digital scroll compressor Only DO5 or DO6 Copeland Stream compressor The signal can also be used to con...

Page 4: ...nsmissores de press o Ratiometric 10 90 do fornecimento AKS 32R Sinal 1 5 V AKS 32 fonte de alimenta o 0 20 mA 4 20 mA AKS 33 forneci mento 12 V Sensor de temperatura Pt 1000 ohm AKS 11 ou AKS 21 NTC...

Page 5: ...poder ser aumentado se necess rio A capacidade do compressor de rolagem digital Somente para DO5 ou DO6 Copeland Compressor de fluxo O sinal de tamb m pode ser usado para controlar um compressor de fl...

Page 6: ...lussstr me Verwenden Sie doppelt isolierte Transformatoren Die Sekund rseite darf nicht geerdet sein Beziehen Sie 0 10 Volt von den Terminals N und AO3 bezie hungsweise N und AO4 ACHTEN SIE AUF DIE PO...

Page 7: ...arf weiter erh ht werden K hlung Keine K hlung Die Leistung aus dem Digital Scroll Verdichter Nur DO5 oder DO6 Copeland Stream Verdichter Das Puls signal kann auch dazu verwendet werden um einen Strea...

Page 8: ...le isolation Le c t secondaire ne doit pas tre mis la terre Obtenir 0 10 V des bornes N et AO3 respectivement N et AO4 VEILLER LA POLARIT DE N AI 4 entr es analogiques AI1 AI4 Transmetteurs de pressio...

Page 9: ...O5 ou DO6 r ducteur de puissance 1 r ducteur de puissance 2 La r duction de puissance 2 suit la r duction de puissance 1 mais avec un d calage d une demi p riode La capacit est divis e en p riodes de...

Page 10: ...transformador con aisla miento doble El lado secundario no debe conectarse a tierra Obtenga 0 10 V de los terminales N y AO3 respectivamente N y AO4 F JESE EN LA POLARIDAD DE N AI Entradas anal gicas...

Page 11: ...necesario este valor se puede aumentar Capacidad del compresor scroll digital Solo DO5 o DO6 Terminaci n conectar H R Terminaci n conectar H R Importante Refrigeraci n Sin refrigeraci n Min capacidad...

Page 12: ...AK PC 551 ADAP KOOL The Product contains electrical components And may not be disposed together with domestic waste Equipment must be separate collected with Electrical and Elec tronic waste According...

Reviews: