66
RS8GV202 © Danfoss 2016-06
AK-LM 340
5. Configuration of Analog
outputs
Press the
+
-button to go on to
the next page
6. Configuration of Analog
input signals
Configuration - continued
5 - Analog inputs
The possible signals are the
following:
0-10V
2-10V
0-5V
1-5V
Stepper output
User defined
6 - Analog inputs
The possible signals are the
following:
Temperature sensors
:
S1 -
Setting:
• Pt1000
• PTC 1000
Pressure transmitters::
P1 -
Setting:
• AKS 32, -1 – 6 Bar
• AKS 32R, -1 – 6 Bar
• AKS 32, - 1 – 9 Bar
• AKS 32R, -1 – 9 Bar
• AKS 32, - 1 – 12 Bar
• AKS 32R, -1 – 12 Bar
• AKS 32, - 1 – 20 Bar
• AKS 32R, -1 – 20 Bar
• AKS 32, - 1 – 34 Bar
• AKS 32R, -1 – 34 Bar
• AKS 32, - 1 – 50 Bar
• AKS 32R, -1 – 50 Bar
• AKS 2050, -1 – 59 Bar
• AKS 2050, -1 – 99 Bar
• AKS 2050, -1 – 159 Bar
• User defined (only ratio-
metric. The min. and max.
values of the pressure
interval must be set).
Voltage signals:
Voltage input 1 -
Setting:
• 0 - 5
• 1 - 5
• 0 - 10
• 2 - 10
We set up the analog inputs for the sensors
In our example, it is not necessary to set the refrigerant.
It is only necessary to set the refrigerant for a PI regulation in which a
conversion between pressure and temperature must be made.
Analog outputs
Output
Module Point
Type
AO_
Step_
Analoge signals
Inlet
Module Point
Type
S1
AI1
1
1
Pt 1000
S2
AI2
1
2
Pt 1000
S3
AI3
1
3
Pt 1000
S4
AI4
1
4
Pt 1000
AI5
1
5
AI6
1
6
P1
AI7
1
7
AKS 32R-12
AI8
1
8
AI9
1
9
AI10
1
10
P2
AI11
1
11
AKS 32R-12
(There are no AO - output signals in the example)