AK-LM 340
RS8GV202 © Danfoss 2016-06
89
Operating AKM / Service tool
The setup of the controller itself can only be carried out via AK-ST
500 service tool software. The operation is described in fitters on
site guide.
If the controller is included in a network with an AKA gateway one
can subsequently carry out the daily operation of the controller
via AKM system software, i.e. one can see and change daily read-
outs/settings.
Note: AKM system software does not provide access to
configuration settings of the controller.
Measurements from all of the signals received and from the most
important displays of the individual functions can be seen.
All alarms can be received by AKM.
Authorisation / Passwords
The controller can be operated with System software type AKM
and service tool software AK-ST 500.
Both methods of operation provide the possibility for access
to several levels according to the user’s insight into the various
functions.
System software type AKM:
The various users are defined here with initials and key word.
Access is then opened to exactly the functions that the user may
operate.
The operation is described in the AKM manual.
Service tool software AK-ST 500:
The operation is described in fitters on site guide.
When a user is created, the following must be stated:
a) State a user name
b) State a password
c) Select user level
d) Select units – either US (e.g. °F and PSI) or Danfoss SI (°C and
Bar)
e) Select language
Access is given to four user levels.
1) DFLT – Default user – Access without use of password
See daily settings and read-outs.
2) Daily – Daily user
Set selected functions and carry out acknowledgement of alarms.
3) SERV – Service user
All settings in the menu system except for creation of new users
4) SUPV – Supervisor user
All settings including the creation of new users.
■
Power
■
Comm
■
DO1
■
Status
■
DO2
■
Service Tool
■
DO3
■
LON
■
DO4
■
I/O Extension
■
DO5
■
Alarm
■
DO6
■
DO7
■
DO8
■
Service Pin
Slow flash = OK
Quick flash = answer from gateway
remains on for 10 mins after network
registration
Constantly ON = error
Constantly OFF = error
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
Light-emitting diodes on the controller
External communication
Communication to AK-CM 102
Internal communication
between the modules:
Quick flash = error
Constantly On = error
Status of output 1-8
Network installation
Installation considerations
Accidental damage, poor installation, or site conditions, can give
rise to malfunctions of the control system, and ultimately lead to
a plant breakdown.
Every possible safeguard is incorporated into our products to
prevent this. However, a wrong installation, for example, could
still present problems. Electronic controls are no substitute for
normal, good engineering practice.
Danfoss wil not be responsible for any goods, or plant compo-
nents, damaged as a result of the above defects. It is the install-
er's responsibility to check the installation thoroughly, and to fit
the necessary safety devices.
Special reference is made to the necessity of signals to the
controller when the compressor is stopped and to the need of
liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further
advice, etc.