AK-LM 340
Two sensor thermostat
1. Go to Configuration menu
2. Select Two sensor thermostat
3. Two sensor thermostat
3 - Two sensor thermostat
The general two-sensor thermostats can be used for
functions with relay outputs.
The following is to be set/read for each two-sensor
thermostat:
• Name
• Define the sensor to be used for cut-in tem-
perature
• Cut in direction
Select whether the relay cut-in is to occur when
temperatures higher or lower than the setpoint
are recorded
• Cut in set point
The relay cuts in when the measurement has
been over (or under) the value for the entire delay
period
• Cut in delay
• Delay period for two consecutive cut-ins
• Select the sensor to be used for cut-out tem-
perature
• Cut out direction
Choose whether the relay cut-out is to occur
when the temperature is recorded higher or lower
than the set value.
• Cut out set point
The relay cuts out when the measurement has
been above (or below) the value for the entire
delay period.
• Cut out delay
• DI -input for stop of function
The regulation stops immediately when a signal is
received. Delay time will not be considered.
In our example we use the settings shown.
Configuration - continued