Danfoss 73691330 Operating Manual Download Page 5

© Danfoss | 2016.11 | 5

VI.CV.E2.8X 

AME 85 QM

ENGLISH

Safety Note

To avoid injury of persons and 
damages to the device, it is absolutely 
necessary to read and observe these 

instructions carefully.
Necessary assembly, start-up, and maintenance 
work must be performed by qualified and 
authorized personnel only.
Please comply with the instructions of the 
system manufacturer or system operator.

Do not remove the cover before the 
power supply is fully switched off.

Disposal instruction

This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 
disposal. 

Always follow the local disposal regulations.

Mounting 

Fix the AME 85, AME 86 on the valve

 

.

Admissible Installation Positions

 

.

Manual override 

The manual override is applied by rotating the 
8 mm Allen key (not supplied) to the required 
position. Observe the direction of rotation 
symbol.

Wiring 

Do not touch anything on the PCB!
Switch off the power line before wire 
the actuator! Lethal voltage!

Wire the actuator according to the wiring

 

diagram.

Control signal
Control signal from the controller must be 
connected to terminals Y (input signal) and SN 
(common) on the AME printed board.
Output signal
Output signal from the terminal X can be used 
for indication of the current position. Range 
depends on the DIP switch settings.
Supply voltage
Supply voltage (24V~ -15 to +10 %, 50 Hz) must 
be connected to the terminals SN and SP.

DIP switch settings 

U

I

2 V_--- V

0 V_--- V

Direct

Inverse

---

Sequential

0(2)_5(6) V

5(6)_10 V

Proportional

3 point/RL

LOG. flow

LIN. flow

100 % k

VS

RED. k

VS

Reset

Reset

 

Factory settings: 

ALL switches are on OFF position!

 

 

Note: 

All combinations of DIP switches are 

allowed. All functions that are selected are added 
consecutively. There is only one logic override of 
functionality i.e. the switch No.6 Proportional /3 
point, which sets actuator to ignore control signal 
and works as a “simple” 3‑point actuator

SW1: U/I 

 

Factory setting: 

Voltage control signal (0‑10 V).

SW2: 2-10 V/0-10 V 

 

Factory setting is:  

2‑10 V.

SW3: Direct/Inverse 

 

Factory setting is:  

DIRECT

SW4: ---/Sequential 

Two actuators can be set to work parallel with 
one control signal. If the SEQUENTIAL is set than 
an actuator responds to split control signal (see 
0(2)-5(6) V/5(6)-10 V).

 

Note: 

This combination works in combination 

with switch No.5: 0(2)‑5(6)V/5(6)‑10 V

SW5: 0(2)-5(6) V/5(6)-10 V 

 

Note: 

This function is available if switch No.4: 

‑‑‑/Sequential is set.

SW6: Proportional/3 point 

When DIP 6 is OFF:

actuator needs to perform self 
stroking prior changing DIP 6 to ON.

Output signal depends on DIP 2, 3&5 setting.

Actuator can operate in modulating (DIP 6 to 
OFF) or in “simple” 3-point mode, if the 3-point 
function is selected (DIP 6 to ON). 
Connect power supply on terminals SN and SP 
terminals.
DIP 6 factory setting is OFF for modulating 
operation.
Actuator’s stem will run to its totally extended 
or retracted position by bridging SN signal to 

terminals 1 or 3 and will remain in this position 
as long as potential is present. 
Set DIP 6 to ON for operating actuator in 3 point 
mode.
Look carefully wiring diagram as wiring is 
different for controllers with triac output (ECL) 
in comparison to controllers with relay output.

 

Note: 

If 3 point function is selected actuator 

does not respond to any control signal on port Y. 
It only rises and lowers spindle if power is supplied 
on port 1 or 3

SW7: LOG. flow/LIN. flow 

 

Factory setting is:  

LOG. Flow (characteristic of valve is unchanged)

 

Note:

 If this function is used in combination 

with non‑logarithmic valves the characteristic of 
motorised valve will be anti‑logarithm of valve’s 
characteristic (e.g. valve with linear characteristic 
will be transformed to quick open characteristic). 

SW8: 100 % K

VS

/RED. K

VS

 

 

Note:

 

 This function works proper only with 

logarithmic (equal percentage) valves. 

SW9: Reset 

After the actuator has been connected to 
power supply, the actuator will start the 
self-adjustment procedure. The indicator LED 
flashes until self adjustment is finished. The 
duration depends on the spindle travel and will 
normally last a few minutes. The stroke length 
of the valve is stored in the memory after self 
adjustment has been completed. To restart 
self adjustment, change the position of RESET 
switch (switch No.9). If the supply voltage is 
switched off or falls below 80 % in more than 
0,1 s, the current valve position will be stored 
in the memory and all data remain saved in the 
memory also after a power supply cut-out.

Function test

The indicator light shows whether the 
positioner is in operation or not. Moreover, the 
indicator shows the control status and faults.

Constant light

-  normal operation

No light 

-  no operation or no power supply

Intermittent light (1 Hz)  

-  self adjusting-mode

Intermittent light (3 Hz): 

-  power supply too low
-  insufficient valve stroke (<20 s)
-  end-position cannot be reached.

Dimensions 

Part Name

Hazardous Substances Table

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hexavalent Chromium (Cr(VI))

Polybrominated biphenyls (PBB)

Polybrominated diphenyl ethers (PBDE)

Guides

X

O

O

O

O

O

Position indicators

X

O

O

O

O

O

Gears

X

O

O

O

O

O

Bushings

X

O

O

O

O

O

O:  Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X:  Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirement in GB/T 26572;

Summary of Contents for 73691330

Page 1: ...S AME 85 QM www danfoss nl Bladzijde 8 ESPA OL AME 85 QM www danfoss es P gina 9 ITALIANO AME 85 QM www danfoss it Pagina 10 POLSKI AME 85 QM www heating danfoss pl Strona 11 ESKY AME 85 QM www cz dan...

Page 2: ...Proportional 3 point RL SN 0 V Neutral SP 24 VAC Power supply Y 0 2 10 V Input 0 4 20 mA 1 0 V Input 3 X 0 2 10 V Output MAINTENANCE FREE 5 95 RH no condensing AUTO 4 6mm 1mm 8 mm HN 10 8 mm AC 24 V C...

Page 3: ...Danfoss 2016 11 3 VI CV E2 8X AME 85 QM Proportional 3 point RL SN 0 V Neutral SP 24 VAC Power supply 1 24 VAC Input 3 X 0 2 10 VDC Output...

Page 4: ...4 Danfoss 2016 11 VI CV E2 8X AME 85 QM H 167 183 103 82 57 30 191 5 min 530 412 403 min 137 max 85 22 AME 85 QM AB QM DN 200 250 Type H mm DN 200 618 DN 250 708...

Page 5: ...in simple 3 point mode if the 3 point function is selected DIP 6 to ON Connect power supply on terminals SN and SP terminals DIP 6 factory setting is OFF for modulating operation Actuator s stem will...

Page 6: ...ter No 5 0 2 5 6 V 5 6 10 V SW5 0 2 5 6 V 5 6 10 V BEMERKUNG diese Funktion ist wirksam wenn der Schalter No 4 Sequentiell eingestellt ist SW6 Proportion l 3 Punkt WennderDIP 6istaufStellmotor mussVen...

Page 7: ...10 V REMARQUE Cette fonction est disponible si la commande 4 S quentiel est r gl e SW6 Proportionnel 3 points LorsqueleDIP6estSURActuateur doitex cuterautor gulationavantle DIPenperp tuelle volution6...

Page 8: ...ke de motor instelt als simpele 3 punts servomotor SW1 U I Fabrieksinstelling 0 10 V stuursignaal SW2 2V 10 0V 10 De fabrieksinstelling is 2 10V SW3 Direct Omgekeerd De fabrieksinstelling is Direct SW...

Page 9: ...posible al elegir el interruptor No 4 Secuencial SW6 Proporcional 3 v as CuandolosinterruptoresDIP6esde actuadordeberealizarajuste autom ticodelalongituddecarrera antesdelconmutadorDIP6enlaposici nON...

Page 10: ...n parallelo con lo stesso segnale di comando Se settata la funzione SEQUENZIALE allora l attuatore risponde al segnale di comando split vedi 0 2 5 6 V 5 6 10 V NOTA Questa combinazione va associata al...

Page 11: ...V UWAGA Ta funkcja jest dost pna gdy ustawiony jest prze cznik nr 4 Sequential SW6 Proportional 3 point Gdyprze cznikDIP6jestNA Si ownikmusiwykonywa samodostrajaniaprzedzmian ustawie prze cznikaDIP6na...

Page 12: ...leln s jedn m dic m sign lem Pokud je nastaven do polohy ON pracuje servopohon v sekven n m rozsahu 0 2 5 6 V nebo 0 4 10 12 mA nebo 6 6 10V nebo 10 12 20mA Pozn mka Tato kombinace pracuje spolu se sp...

Page 13: ...SW3 Egyenes Ford tott A gy ri be ll t s EGYENES SW4 Szekvenci lis K t szelepmozgat p rhuzamos m k d sre ll that egy vez rl jellel m k dtetve SZEKVENCI LISRA ll tott helyzetben a szelepmozgat gy reag...

Page 14: ...SP DIP U I 2 V_ V 0 V_ V 0 2 V_5 6 V 5 6 V_10 V RL LOG flow LIN flow 100 kVS RED kVS Reset Reset OFF DIP 6 SW1 U I SW2 2 10 V 0 10 V 2 10 V SW3 SW4 0 2 5 6 V 5 6 10 V 5 0 2 V 5 6V 5 6 V 10 V SW5 0 2...

Page 15: ...V_ V 0 V_ V 0 2 V_5 6 V 5 6 V_10 V 3 RL 100 Kvs Red Kvs OFF DIP 6 SW1 U I 0 10 B SW2 2 10B 0 10 B 2 10 B SW3 SW4 0 2 5 6 5 6 10 5 0 2 5 6 5 6 10 SW5 0 2 5 6 5 6 10 4 SW6 DIP 6 DIP 2 35 DIP6 6 OFF 3 3...

Page 16: ...eserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agre...

Reviews: