WARNING
ELECTRICAL SHOCK HAZARD
VLT
®
series drives contain dangerous voltages when
connected to mains voltage. Improper installation, and
installing or servicing with power connected, can cause
death, serious injury, or equipment failure.
To avoid death, serious injury, or equipment failure:
•
Only use qualified electricians for the installation.
•
Disconnect the drive from all power sources before
installation or service.
•
Treat the drive as live whenever the mains voltage
is connected.
•
Follow the guidelines in these instructions and local
electrical safety codes.
NOTICE
APPLYING GASKETS
This kit contains gaskets to ensure a proper seal between
metal parts. Before adhering a gasket to a part, check that
the part matches the gasket and that no holes are covered.
Installation Instructions
Installing the Top Cover Plate
To install the top cover plate of the cooling kit, use the
following procedure. See
Illustration 1.2
.
1.
Remove paper backing from the top gasket to
expose the adhesive. Adhere the top gasket to the
underside of the top cover plate.
2.
Remove 6 M5x12 screws (T25) surrounding the sides
and back of the vent in the top surface of the drive
enclosure. Retain the screws.
3.
Loosen 3 M5x12 screws (T25) at the front of the vent
in the top surface of the drive enclosure.
4.
Slide the edge of the top cover plate under the 3
loosened screws, positioning the plate over the vent
in the top surface of the enclosure.
5.
Secure the top cover plate to the enclosure with the
6 M5x12 screws (T25) removed previously. Torque
fasteners to 2.3 Nm (20 in-lb).
Installation Instructions
In-back/Out-back Cooling Kit for E1h/E2h Drives
VLT
®
Series FC 102, FC 103, FC 202, and FC 302
2
Danfoss A/S © 09/2017 All rights reserved.
MI35D102