Sundanzer Refrigerator/Freezer Troubleshooting Tips 

 

 

When the power is connected to the unit, does it attempt to start at all?  

Does it run a short period of time then shut off without cooling much?  

Does it run non-stop, never shut off and not cool?

 

You can also remove the side plastic grill and remove to screw that retains the 
Electronic Control Unit (ECU) on the compressor. Then unplug the ECU from the 
compressor and check the resistance on the compressor pins. It should be about 
2.5 ohms between all three pairs: 1&2,2&3 and 1&3.  

If so, the compressor should be fine. The most common failure is from low-
voltage disconnect. This can happen from oxidized connections, even when it 
has been working fine for some time and sometimes it may be intermittent. 
Disconnect, clean and reconnect all connections.  

See the attached spec sheet for the Electronics Unit. 

  

  

 

Summary of Contents for 101N0210

Page 1: ...Electronic Control Unit ECU on the compressor Then unplug the ECU from the compressor and check the resistance on the compressor pins It should be about 2 5 ohms between all three pairs 1 2 2 3 and 1...

Page 2: ...hermostat Fig 1 The thermostat 7 is connected between the terminals C and T Without any resistor in the control circuit the compressor with electronic unit 101N0210 or 101N0220 will run with a fixed s...

Page 3: ...ereich von 9 6 bis 31 5V Thermostat Abb 1 Der Thermostat 7 wird an die Anschlu klem men C und T angeschlossen Ohne einen Wider stand im Steuerkreis l uft der Verdichter mit elek tronischer Steuerungse...

Page 4: ...tance de 220 k est recommand e En mode de vitesse AEO Adaptation Energie Opti mis e le compresseur BD modulera toujours sa vitesse de rotation en fonction de la demande de froid sur une plage de tensi...

Page 5: ...ad a la demanda de refrigeraci n actual dentro de un rango de tensi n de funcionamiento de 9 6 a 31 5 V Termostato fig 1 El termostato 7 est conectado entre los termi nales C y T Sin resistencia en el...

Page 6: ...Nella modalit AEO ottimi zzazione energetica mediante controllo adatta tivo il compressore BD adatter sempre la pro pria velocit alla reale richiesta di resa frigorifera entro una tensione d esercizio...

Page 7: ...ruikt wordt zonder batterij is een weerstand van 220 k aanbevolen In AEO Adaptive Energy Optimizing modus past de compressor zijn snelheid altijd aan in functie van de vraag naar koeling en dit binnen...

Page 8: ...lk rlig driftssp nding fra 9 6 til 31 5V Termostat fig 1 Termostaten 7 tilsluttes mellem klemme C og T Uden modstand i kontrolkredsl bet arbejder kompressoren med den elektroniske enhed 101N0210 eller...

Page 9: ...varvtalet till aktuellt kylbehov inom sp nningsomr det 9 6 till 31 5 volt Termostat fig 1 Termostaten 7 r ansluten mellan anslutning arna C och T Utan motst nd i kontrollkretsen kommer kompressorn me...

Page 10: ...la 101N0210 tai 101N0220 py rii vakionopeudella 2000 kierr min termostaatin ollessa kytkettyn p lle Kun termostaatti on suoraan kytketty C liitimeen s hk osa 101N0300 s t nopeuden todellisen kylm tarp...

Reviews: