Refrigeration and Air Conditioning Controls 

DKRCCPICD0A122

Instructions

060R9769

060R9769

Product Specifi cation

KPU Temperature Controls

Application

KPU temperature controls are used for regulation and to ensure 
safety in refrigeration, freezing, air conditioning, ventilating and 
heating systems.
KPU temperature controls are available with vapor charge or with 
adsorption charge.
All KPU temperature controls are fi tted with Single-Pole Double-
Throw (SPDT) switches.

For large ac motors and for all dc motors, KPU is installed in the 
control circuit. For single phase ac motors, KPU is installed in the 
line voltage supply to the motor.

The standard KPU enclosure is rated NEMA 1. NEMA 2 is obtained 
when the control is mounted on a fl at surface. When mounting 
KPU on a bracket, cover all unused holes. 

Charge

Type

Code no.

Bulb type

Capillary 

tube length

[in.]

Reset 

function

Regulating 

range

[F˚]

Diff erential 

Δt

 [°F]

Max. bulb 

temperature

[°F]

Ambient 

temperature

[°F]

Vapor

KPU 61

060L5201

A

80

auto.

–20 

 60

 18**

250

–40

122

(170 for max. 

2 hours)

KPU 61

060L5202

A

200

auto.

–20 

 60

 18**

KPU 61

060L5203

B

80

auto.

–20 

 60

 18**

KPU 61B

060L5204

B

80

man. (MIN)*

–20 

 60

5 (fi xed)**

KPU 61B

060L5205

B

200

man. (MIN)*

–20 

 60

5 (fi xed)**

KPU 61

060L5210

B

80

auto.

–20 

 60

 18**

KPU 62

060L5206

C1

0

auto.

–20 

 60

 18**

KPU 63

060L5213

A

80

auto.

–60 

 15

10 

 25**

KPU 63

060L5214

B

80

auto.

–60 

 15

10 

 25**

KPU 68

060L5215

C1

0

auto.

25 

 95

 22**

KPU 69

060L5217

B

80

auto.

25 

 95

 22**

Adsorption

KPU 62

060L5207

C2

0

auto.

–20 

 60

 15

175

KPU 73

060L5208

E3

80

auto.

–15 

 60

→ 

35 

KPU 73

060L5209

E1

80

auto.

–15 

 60

15 

 45

KPU 73B

060L5211

E3

80

man. (MIN)*

–15 

 60

6 (fi xed)

KPU 73

060L5212

D

80

auto.

–15 

 60

 35

KPU 71

060L5218

E2

80

auto.

25 

 70

 18

KPU 71B

060L5216

E2

80

man. (MIN)*

25 

 70

5 (fi xed)

KPU 74

060L5219

E1

80

auto.

 80

 35

KPU 74B

060L5220

E1

80

man. (MIN)*

 80

10 (fi xed)

KPU 75

060L5221

F

80

auto.

30 

 95

 18

230

KPU 75

060L5222

E2

80

auto.

30 

 95

 18

KPU 77

060L5223

E3

80

auto.

60 

 140

 18

265

*   man.(MIN): Manual reset after cut-out on falling temperature
**  The switch diff erential is dependent on range settings. Low range settings increases the diff erential. High range settings decreases the 
 diff erential. Use the graphs on page 3 to determine the correct diff erential setting. 

Thermostat bulb types

A

B

C

D

E

F

straight capillary tube

remote air coil

air coil/ room sensor

double contact remote coil

remote bulb

remote duct coil