Adjustment

NOTE: 

Adjust the temperature control to settings specifi ed by 
the manufacturer of the controlled equipment. When 
checking temperature control operation, or operating the 
controlled equipment, do not exceed the manufacturer’s 
temperature ratings for the controlled equipment or for 
any of its components.
To avoid inaccurate control operation, do not adjust the 
KPU’s pointers beyond the highest or lowest indicator 
marks on the scale plate.

Before adjustment loosen the locking screw.
For setting use Universal Refrigeration Wrench or the setting knob, 
if available.
Movement of the setting knob is limited by the locking screw, 
which allows only small corrections to the settings. Therefore, if 
the setting knob is to be used for adjustments, completely remove 
the locking screw. After adjustment, tighten the locking screw.

Adjustment: Temperature Control with automatic reset

Scale plate directly indicates High Switching Point and  
Diff erential.

3. Low Switching Point is equal to High Switching Point less 
Diff erential:                   LOW = HIGH - DIFFERENTIAL

Diff erential adjusting 
screw

Setting knob

Locking screw

Range adjusting 
screw

Cover screw

1. Set High 
Switching Point 
by adjusting 
range screw.
Turn the screw 
clockwise to 
lower the set 
point.

2. Then set 
Diff erential by 
adjusting 
diff erential screw. 
Turn the screw 
clockwise to in-
crease Diff erential.

Adjustment: Temperature Control with manual reset

Scale plate directly indicates Low Switching Point, which is  
Cut-Out. There is no pointer for Diff erential. 
Diff erential value is fi xed and printed on the scale plate.

1. Set Cut-Out 
(Low Switching Point) by 
adjusting range screw.
Turn the screw clockwise 
to lower the set point.

2. High Switching Point (Cut-In) equals Low Switching Point 
(Cut-Out) plus Diff erential:       
 

 

 CUT IN = CUT OUT + DIFFERENTIAL

IMPORTANT

:

The scale plate is only for reference and for more precise 
setting a temperature gauge should be used.

IMPORTANT

After installing and adjusting the temperature control, 
check your settings by running the controlled equipment 
several times (at least three times) under normal operating 
conditions. 

Manual switch

Available only on KPU61 (060L5210) and KPU62 (060L5207), the 
manual switch is a two-position switch used to shut down the 
refrigeration system. The two positions are:
1) AUTO: position for automatic operation 
2) STOP: contacts 1 and 2 are locked in the closed position.

CAUTION:

The manual switch only stops automatic operation, and can 
only be used for service on non-electrical parts. Interrupt 
mains power before servicing electrical parts.

manual 
switch