Installation manual for DM700 ECDIS
Copyright Danelec Marine A/S
MAN11805-10
Page 34/67
A sensor has the following parameters:
a)
Priority
– Priority of the sensor if several sensors of the same type are registered; if the
sensor with the highest priority is lost, the sensor with the next priority is used instead;
b)
Timeout
– Time period between the loss of connection with the sensor and the triggering of
the alarm “Invalid data”;
c)
Talker ID
– ID of the sensor used to distinguish between sensors of the same type, or
sensors sending the same NMEA sentences;
d)
Description
– Description of the sensor;
e)
Line name
– Name of the connection line;
f)
Sensor
location
– Position of the sensor on board the own vessel relative to the conning
station:
a positive X value indicates the position of the sensor between the conning station and
the starboard;
a negative X value indicates the position of the sensor between the conning station
and the port board;
a positive Y value indicates the position of the sensor between the conning station and
the bow;
a negative Y value indicates the position of the sensor between the conning station
and the stern;
g)
Mnemonic
– NMEA sentences to listen to;
h)
Checksum
– Indicates that checksum of the sentences should be checked: if the checksum
of a sentence is wrong, the sentence is ignored; if the option is off, all sentences are
processed.
6.4.2 Line monitor
To check if the communication line of a sensor operates, use the line monitor.
1.
Go to
Main Menu
Settings
Vessel
Sensors
: the
Sensors
panel opens.
2.
Select the sensor whose communication line you want to check: the sensor parameters
panel opens.
3.
Press the
[Line monitor]
button in the upper right corner of the panel: the
Line monitor
panel opens. If the communication line operates, NMEA sentences coming from the sensor
are displayed in the panel.
4.
To pause NMEA sentences, press the
[Pause]
button: new sentences are no longer
displayed and the
[Pause]
button changes to
[Resume]
.
5.
To resume NMEA sentences, press the
[Resume]
button: if the communication line
operates, new NMEA sentences are displayed.
6.
To clear all sentences from the panel, press the
[Clear]
button: the panel is cleared.
Summary of Contents for DM700 ECDIS
Page 61: ...Installation manual for DM700 ECDIS Copyright Danelec Marine A S MAN11805 10 Page 61 67...
Page 63: ...Installation manual for DM700 ECDIS Copyright Danelec Marine A S MAN11805 10 Page 63 67...
Page 65: ...Installation manual for DM700 ECDIS Copyright Danelec Marine A S MAN11805 10 Page 65 67...
Page 66: ...Installation manual for DM700 ECDIS Copyright Danelec Marine A S MAN11805 10 Page 66 67...
Page 67: ...Installation manual for DM700 ECDIS Copyright Danelec Marine A S MAN11805 10 Page 67 67...