Input signal Ud = (output value - 32768) / 32768 * 10.5 mV/V;
Measuring range 0.0 to 5 V
Measuring range 0-5 V (set_gain 0xB2 <p1> <p2>) with p1=ch, p2=0x03
Input signal in V
Measuring range in %
16 Bit output value (hexadecimal)
5.25
105.00%
FFFFh
5.0
100.00%
F9E7h
0.0
0.00%
8000h
Conversion of digital output value to analogue input signal:
Output value = Highbyte * 256 + Lowbyte;
Input signal Ud = (output value - 32768) / 32768 * 5.25 V;
Measuring range 0.0 to 10 V
Measuring range 0-10 V (set_gain 0xB2 <p1> <p2>) with p1=ch, p2=0x07
Input signal in V
Measuring range in %
16 Bit output value (hexadecimal)
10.5
105.00%
FFFFh
10
100.00%
F9E7h
0.0
0.00%
8000h
Conversion of digital output value to analogue input signal:
Output value = Highbyte * 256 + Lowbyte;
Input signal Ue = (output value - 32768) / 32768 * 10.5 V;
Measuring range PT1000
Measuring range PT1000 (set_gain 0xB2 <p1> <p2>) with p1=ch, p2=0x04
Input signal in °C
Measuring range in %
16 Bit output value (hexadecimal)
1050
105%
FFFFh
1000
100%
F9E7h
0.0
0.0%
8000h
-40
-4%
6DB0h
Conversion of digital output value to analogue input signal:
Output value = Highbyte * 256 + Lowbyte;
Input signal Ue = (output value - 32768) / 32768 * 1050 °C;
Measuring range K thermocouple cable
Measuring range K-thermocouple cable (set_gain 0xB2 <p1> <p2>) with p1=ch,
p2=0x06
Input signal in °C
Measuring range in %
16 Bit output value (hexadecimal)