Setting Parameter
Description
Battery Number
Set the number of batteries on a string
2x16
2x17
2x18
2x19
2x20
Battery Group
Set the number of battery strings in a group
1
2
3
4
5
6
7
8
Single Battery
Capability
Battery capacity: _ _ _ _ Ah (range 7 to 2000)
Boost upper limit
Volt.
Set the upper limit voltage in boost mode
2.27 V/cell (default, range 2.20 to 2.40)
Float base Volt.
Set the float mode voltage
2.27 V/cell (default, range 2.20 to 2.29)
Battery Protect Volt.
Set the end of discharge voltage
1.65 V/cell (default, range 1.20 to 1.90)
Boost Charge
Boost charges the batteries at the end of a recharge
Enable (default) Disable (use for VRLA batteries)
Shutdown Pre Alarm
Time
Set the number of minutes before a predicted shutdown that an alarm is given. The
prediction is based on the battery capacity and load.
Time (1 to 99): _ _ (minutes)
Max charge current
Set to 10% of the battery Ah capacity rating in amperes.
_ _ A (E420 and E430, 1 to 15 A; E440, E460 and E480, 1 to 30 A in 1 A steps)
LCD display messages
Display messages appear on the bottom line of the LCD display.
Display
Meaning
CurState: Init
Initialisation
No-Out
No output
Bypass
UPS in bypass mode
Mains
Rectifier working
Battery
Battery invert
Testing
Battery test in progress
Starting
Starting
CurState: ECO
UPS running in ECO power saving mode
CurState: EPO
Emergency Power OFF mode
CurState: M-Byp
UPS in maintenance bypass mode
CurState: Fault
UPS fault
Battery Charging
Battery float charging
Battery Boost
Battery boost charging
Invter ON/ Invter OFF
Inverter working or not
Inver Master
Master of multi UPS system
SWMB ON/ SWMB OFF Maintenance switch close or open