3. Below the black start switch on each UPS, remove the plate that covers the parallel connectors.
4. Connect the CAN bus, labelled
Parallel Port 1
and
Parallel Port 2
, in a ring arrangement using the
supplied cables as shown below. Make sure you wire all CAN bus connectors and secure them in
place using their captive screw locks.
5. Replace the protective cover to protect the CAN bus cables against accidental removal.
6. Optional connection. You can control and monitor all units using the RS232 port on one UPS. To do
this, connect the RS485 socket of one unit to RS485 socket of the next unit and so on until all units
are connected in a daisy-chain as shown below.
Note:
Do not connect the units in a loop.