Press the “Inquiry” button 10 seconds, enter into the parameter setting state of the 

administrative class 

 

Parameter  Instruction 

Range 

Default  

Mark 

P01 

Back temp adjustment 

 15

 

3

 

P02 

Temp precision adjustment 

 15

 

0

 

P03 

Heating water flow insufficient temp. 

difference protection adjustment 

5

 60

 15

 

P04 

Cooling water flow insufficient temp. 

difference protection adjustment 

 60

 12

 

P05 

Entering defrosting temp. adjustment 

 7

 

2

 

P06 

Defrosting end temp. adjustment 

2

 25

 12

 

P07 

Defrosting interval time adjustment 

20 

 80 min 

45min 

P08 

Defrosting running time adjustment 

 15 min 

6min 

P09 

Compressor exhaust protection temp. 

adjustment 

100 

 125

 110

 

P10 

low pressure time set 

1

15min 5min 

P11 

low pressure environment temp. 

adjustment 

10

0

 

5

 

P12  

Over cool protection temp. 

adjustment 

1

15

 

5

 

P13 

Overheating protection temp. 

adjustment 

50

85

 65

 

P14 

P12 and P13 unrecoverable 

protection times adjustment 0

5  

 5 

P50 

Selecting of restart function when 

outage  

0[No] 1[Yes] 

P51 

Background light selecting of the 

display screen 

1[light 15s] 

0[light 

constantly] 

Adjust 

through  

“up/down

” button 

 

 

Summary of Contents for DSP? 85HA

Page 1: ...Air Source Swimming pool Heat Pump Installation and Operation Manual DSP 85HA DSP 100HA DSP 120HA...

Page 2: ...1 Content Safety Precautions 2 Technical data 3 Unit dimension 4 Installation 5 Sound pressure level 8 Electric connection 9 Controller instruction 11 Maintenance Troubleshooting 15...

Page 3: ...n of installation is stable If the foundation is unstable the outdoor unit may drop and cause a casualty Make sure that the electric leakage protection switch is fixed If no electric leakage protectio...

Page 4: ...nning Temp Range 5 43 Unit Dimension W H D mm 615 1060 370 Net Weight KG 55 62 70 Noise dB A 52 54 54 Water Inlet Outlet Dimension 50 8 2 Water Heat Exchanger Titanium Min Water Flow L MIN 60 72 80 Re...

Page 5: ...4 Unit dimensions Model A mm B mm C mm D mm E mm DSP 85 HA DSP 100 HA DSP 120HA 650 1140 415 435 684...

Page 6: ...al safety 4 Ensure the unit is well ventilated direction of air exhaust is kept away from windows of neighboring buildings and the exhaust air cannot flow back Moreover adequate service clearance shou...

Page 7: ...6 Installation in exceptional circumstances unit mm No obstacle in front of the unit Obstacle above the unit Obstacle in front of the unit Several units in a row...

Page 8: ...7 Installation diagram Installation diagram for combination...

Page 9: ...d a place on the side that faces the least sound sensitive neighbor area The sound pressure levels are further affected by walls bricks differences in ground level etc and should therefore only be see...

Page 10: ...er with at least a 3 mm breaking gap Incoming supply must be 220V 1 phase neutral ground via a distribution board with fuses If an insulation test is to be carried out in the building please make sure...

Page 11: ...10 Circuit drawing...

Page 12: ...me When the timer on timer off are set press this button the unit will start or stop according to the set time everyday Press again to cancel it Time Press time button it shows clock Press up or down...

Page 13: ...FF to quit defrosting mode compulsively Note the unit is of defrosting automatic function so only when defrosting incompletely in winter is the compulsively defrosting needed This operation must be fo...

Page 14: ...ting end temp adjustment 2 25 12 P07 Defrosting interval time adjustment 20 80 min 45min P08 Defrosting running time adjustment 3 15 min 6min P09 Compressor exhaust protection temp adjustment 100 125...

Page 15: ...0 No 1 Yes 1 P54 Function selecting of exhaust temp protection 0 No 1 Yes 1 P55 Water flow switch 0 No 1 Yes 1 P56 Water pump open constantly option 1 open constantly 0 open close normally 1 Adjust th...

Page 16: ...ating exchanger regularly to maintain good heat exchange as conserve energy The operation pressure of the refrigerant system should only be serviced by a certified technician Check the power supply an...

Page 17: ...07 Outlet water temp E09 Water flow insufficient E10 Communication failure E14 Compressor exhaust temp E25 Outlet water overcooling protection in the cooling mode E26 Outlet water overheating protecti...

Reviews: