Swimming pool heat pump 

 

- 22 - 

 

Code 

Fault 

Check 

Solution   

EE 01 

or EE 

High 

pressure 

protection   

10.

 

On  heating  code:  check  if  there 
is  jam  in  water  circuit  system  or 
the water flow not enough 

11.

 

On cooling mode: check 
evaporimeter, the fan and elated 
components and air flow 

12.

 

Check the connecting wire 

13.

 

Check  if  high  pressure  switch  is 
broken 

14.

 

Check if refrigerant circuit jams. 

1.

 

Remove jam or adjust 
the water flow bigger. 

2.

 

Clean the 
evaporimeter 
regularly, make sure 
the fan runs well and 
there is enough 
sufficient air 
circulation (see 
manual for details) 

3.

 

Reconnect the wire. 

4.

 

Replace  it  with  new 
high pressure switch. 

5.

 

It 

is 

done 

by 

professionals. 

EE 02 

or EE 

Low 

pressure 

protection   

1.

 

Check the connecting wire 

2.

 

Check  if  low  pressure  switch  is 
broken. 

3.

 

Check if lack of refrigerant. 

1.

 

Reconnect the wire 

2.

 

Replace it with a new 
low pressure switch. 

3.

 

Charge 

enough 

refrigerant. 

EE 03 

or EE 

Water flow insufficient 

1.

 

Check  if  there  is  jam  in  water 
circuit. 

2.

 

Check  if  the  back  water  temp. 
sensor  and  outlet  water  temp. 
sensors are set in right position. 

 

1.

 

Remove jam. 

2.

 

Make  sure  these  two 
temp.  sensor  at  right 
position  on  the  heat 
pump. 

EE 08 

or EE 

Communication failure 

Check the connection 

Reconnect the wire. 

Note:   
Failures  related  with  temperature  could  restore  automatically;  when  showing  other  faults, 
need to press “ON/OFF” button to restart. 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for DSP?45HCA

Page 1: ...Air Source Swimming Pool Heat Pump USER MANUAL DSP 45HCA DSP 65HCA DSP 85HCA DSP 100HCA DSP 120HCA DSP 180HCA DSP 180HCA 3 DSP 230HCA DSP 230HCA 3 DSP 260HCA 3...

Page 2: ...p when running It may touch the fan and damage it or lead to accidents especially for the children Do not use the unit without the grid in case it may lead to any accidents 6 For safety reasons please...

Page 3: ...Swimming pool heat pump 2 Content Product brief instruction 3 Technical data 4 Unit dimension 6 Installation 8 Electric connection 13 Controller operation instruction 16 Maintenance Troubleshooting 22...

Page 4: ...l water Your existing water pump circulates the water through the heat pumps heater usually next to the pool equipment and the water warms up This pool heat pump is also of cooling function User can c...

Page 5: ...220 240 1 50 Setting Temp Range 15 45 Running Temp Range 5 43 Water Inlet Outlet Dimension 50 8mm Water Heat Exchanger Titanium Water Flow m3 h 3 4 4 4 5 4 5 Refrigerant R410A Unit Dimension W H D mm...

Page 6: ...Temp Range 5 43 Water Inlet Outlet Dimension 50 8mm Water Heat Exchanger Titanium Water Flow m3 h 7 5 8 5 Refrigerant R410A Unit Dimension W H D mm 820X720X1055 Net Weight KG 119 119 133 133 148 Disp...

Page 7: ...ol heat pump 6 UNIT DIMENSIONS Horizontal models Model A mm B mm C mm D mm E mm DSP 45 HCA 510 306 266 276 410 DSP 65 85 HCA 552 995 284 344 680 DSP 100 HCA 617 1118 350 290 660 DSP 120 HCA 650 1140 4...

Page 8: ...Swimming pool heat pump 7 Vertical models DSP 180HCA DSP 180HCA 3 DSP 230HCA DSP 230HCA 3 DSP 260HCA 3...

Page 9: ...installed on the floor its undercarriage should be heightened to avoid ingression of accumulated water in rainy season In snowy areas it is important to prevent accumulated snow from blocking up the a...

Page 10: ...led anywhere outdoors providing minimum distance requirements are met with respect to other objects For indoor pools please consult your installer Attention Do not place the unit in an enclosed area w...

Page 11: ...hould be avoided as much as possible as machine falling down may result in severe accident Distance from the pool Normally the pool heat pump is installed within a 7 5 meter radius of the swimming poo...

Page 12: ...be lower than the unit standard value please refer to the nameplate 2 The insulation of water pipe should be done well to prevent energy loss 3 A suitable draining valve should be installed in the bot...

Page 13: ...Swimming pool heat pump 12 Project Installation sketch map...

Page 14: ...e neutral ground via a distribution board with fuses If an insulation test is to be carried out in the building please make sure to disconnect the heat pump To avoid the possibility of false action ca...

Page 15: ...Swimming pool heat pump 14 Circuit diagram Model DSP 45HCA DSP 65HCA DSP 85HCA DSP 100HCA DSP 120HCA...

Page 16: ...Swimming pool heat pump 15 Model DSP 180HCA 3 DSP 230HCA 3 DSP 260HCA 3...

Page 17: ...ON or OFF at any state At the ON state press the key into OFF state it shows Clock Working mode and Timer status At the OFF state press the key to start unit it shows Water inlet temp Working mode and...

Page 18: ...quiry interface of parameter and state it exits inquiry interface to enter into main interface if there is no any operation for 8 seconds 1 3 System parameter setting 1 3 1 At inquiry interface if it...

Page 19: ...election parameter 0 Only cold 1 Heat pump 2 E heater 3 Only heat 1 Adjustable 09 Water pump working Mode 0 Normal 1 Special 0 Adjustable 10 Automatic return water temp setting value 8 60 40 Adjustabl...

Page 20: ...is only valid remote controller Parameter table LCD or LED Parameter Meaning Range Default Remark 00 or 0 Cooling return water temp setting value 8 28 12 Adjustable 01 or 1 Heating return water temp...

Page 21: ...mp difference protection PP 06 or PP 6 Bright Cooling anti freezing protection PP 07 or PP 7 Bright Winter first grade anti freezing protection PP 07 or PP 7 Extinguish Winter second grade anti freezi...

Page 22: ...does not occur Discharge the water at the bottom of water pump if the unit will not be used for an extended period of time Check the unit thoroughly and fill the system with water fully before using...

Page 23: ...ire 4 Replace it with new high pressure switch 5 It is done by professionals EE 02 or EE 2 Low pressure protection 1 Check the connecting wire 2 Check if low pressure switch is broken 3 Check if lack...

Page 24: ...DAISHIBA Heating Refrigeration Equipment Co Ltd Web www daishiba com cn Tel 86 757 85213698 Fax 86 757 85213699 Email jenny daishiba com cn Add No 2 Chuangye Nan Road Songxia Industrial Park Songgang...

Reviews: