4
Proline® LEX Series Exit Sign
Installation Guide
Drill a 3/4″ hole through the desired conduit entry knockout
location on the top or side of the frame of the sign.
1
FLEXIBLE CONDUIT ONLY!
Conduit Entry
Route the AC input conduit into housing.
2
All conduit connections must use UL LISTED and SUITABLE
FOR WET LOCATION parts.
3
To finish installation of EXIT sign, reference
Wall, Ceiling
or
End Mount
instructions.
4
Operation (Battery Back-up)
1
Apply AC power to the unit. The LED indicator will be RED. Plug battery into the board and the LED indicator
will turn Green.
2
After the battery has been left to charge for 2 hours, test the unit by pushing the switch. The LED indicator
turns OFF and the LED board stays ON.
3
When the switch is released, the LED indicator will turn to GREEN and the LED board remains ON.