background image

4

Lumination

®

 (LRX - Series) 

Installation Guide

Frame Installation

2

Ensure that the power to the unit is turned off. 

Use proper lockout and tagout procedures.

3

Remove existing downlight fixture. Leave wiring in Junction 

box. Verify that the AC supply line is provided with a 

ground wire connected to the luminaire.

Connect AC and 

dimming conduit

Junction 

LRXEMBB IT07

LXREMBBKIT10

box

Dimming (optional)

AC line

Grounding

Dimming (+)

Unswitched Power (L1)

Common (N)

Switched Power (L2)

Dimming (–)

Black
White
Red
Yellow-Green
Violet
Gray

4

Connect the conduit for the fixture AC and dimming leads to the junction box. Verify that the AC supply line and dimming leads are 

connected properly (see wiring diagram).

Note: 

For phase cut dimming product, dimming leads can be disconnected

•  If dimming leads will not be utilized, please do not remove the wire connectors.

• Dimming compatibility for both 0-10V and phase cut, please refer to Current’s website: www.gecurrent.com/dimming.

Connect AC and 

dimming conduit

Junction 

LRXEMBB IT07

LXREMBBKIT10

box

Dimming (optional)

AC line

Grounding

Dimming (+)

Unswitched Power (L1)

Common (N)

Switched Power (L2)

Dimming (–)

Black
White
Red
Yellow-Green
Violet
Gray

“L” Bridge

Secure 

battery

5

Connect male and female ends of the battery unit

connector. Then the battery will discharge. Please

refer to the picture shown above.

“L” Bridge

Secure 

battery

6

Attach LRXEMBBKIT07HE, LRXEMBBKIT07 or

LRXEMBBKIT10 to existing frame with “L” bridge and

secure IOTA battery to the ceiling. 