Lumination

®

 (LRX - Series) 

Installation Guide

Prepare Electrical Wiring

Electrical Requirements

• The luminaire must be supplied with 120-277 VAC,

   50/60 Hz (In 120-277V application).

• Connected to an individual properly grounded branch    

   circuit, protected by a 15 or 20 ampere circuit breaker. Use  

   min. 75°C supply conductor.

Grounding Instructions

• The grounding and bonding of the overall system

   shall be done in accordance with National Electric

   Code (NEC) Article 600 and local codes.

Fixture Requirements

The units covered by this install instruction are intended to retrofit 

listed surface mounted luminaires, as well as type Non-IC recessed 

mounted fluorescent type luminaires. Please review Step 1 for an 

example existing fixture depiction.

Provided Item

Qty.

1

 LRX EMBB Frame Kit

1

2

 LRX EMBB Fixture

1

Components List

Provided Components

The components have been properly packed to avoid damage during transit. Inspect the components to confirm there is no physical damage. 

Do not install damaged components.

LRXEMBBKIT07HE/LRXEMBBKIT07/LRXEMBBKIT10 Installation

Frame Installation

1

Before retrofit, verify that the junction box and bracket in the 

existing installation are metal and are constructed similarly to 

the illustration above.

Suitable Frame

Bracket

Hole

Suitable 

Fixture

Size (in.) Shape Dimensions (in.) Size (in.)

4

Round

12.60 x 7.64 x 3.54

4.20-5.50 LRXR4xxxxxxx

6

Round

12.60 x 7.64 x 3.54

5.91-6.50 LRXR6xxxxxxx

8

Round

15.55 x 11.34 x 3.54  7.68–8.27 LRXR8xxxxxxx

4

Square

12.60 x 7.64 x 3.54

4.20-5.50 LRXS4xxxxxxx

6

Square 13.35 x 11.34 x 3.54 5.95-7.50 LRXS6xxxxxxx

8

Square 13.35 x 11.34 x 3.54 7.95-9.50 LRXS8xxxxxxx