(5) Excess cable
Better solution
Good solution
Not
recommended
[Figure 9-9] Remaining cable handling method
(6)
Cabling instructions
:
Do not coil excess cable of different types (for example, motor power and feedback) together. An
efficient transformer is formed at HF.
Cable lengths should ideally be trimmed to fit the application.
If excess cable cannot be trimmed, it should be laid in an 'S' or figure eight pattern (refer to the figure
below).
(7) Ferrite core
Ferrite core turn
[Figure 9-10] Ferrite core turn
✏
Note
:
Using ferrite cores, increase the maximum number of turns around the ferrite for optimum
results.
9.4.6.
Earthing
The F.G pin in
a
circle Connector must be wired to the F.G terminal of the SMPS.
Earth pin on LAN1 and LAN2 is a signal Shield.
Earth wire should be used more than 2 mm.
The length of the ground line is as short as possible.
AC Power Earth and control system Ground are must be isolated.
Master
Slave
Master
Slave
√
[Figure 9-11]
Earth wiring methods