6
Dimensional drawing & centre of gravity
6 - 1 Dimensional drawing
3
FXUQ71MA
3D013860D
790 Suspension position
Drain connection
location for upper
piping
Brand name plate (Note 2)
790 Suspension position
1500mm
or more
1500mm
or more
1500mm
or more
1500mm
or more
Required space
1000mm or more (Requierd space)
Height of suspension bracket
Suspension bolt
4-M3~M10
Drain pipe can
be raised up to 0mm from the top surface of the product.
Drain connection
location for rear
piping
When closing the discharge grill, the required space is
30mm or more. (Note 3)
50
NOTES
1
Location for manufacture’s label: on bell mouth.
2
This is where the signal of infrared remote control is received.
Refer to the drawing of infrared remote control in detail.
3
When closing the discharge grill (2 or 3 way discharge), direction of pipe
connection will be limited, please refer to Installation manual..
Nr
Part name
Description
1
Liquid pipe connection
ø9.5 Flare connection
2
Gas pipe connection
ø15.9 Flare connection
3
Drain pipe connection
VP20
4
Air outlet
5
Air suction grille
6
Corner decoration cover
7
Right pipe/wiring connection
8
Rear pipe/wiring connection
9
Pipe through cover
10 Accessory drain elbow
FXUQ100-125MA
3D044898B
Drain connection
location for upper
piping
Drain connection
location for rear
piping
Drain pipe can be
raised up to 500mm from the top surface of the product.
Brand name plate (Note 2)
790 Suspension position
1500mm
or more
1500mm
or more
1500mm
or more
1500mm
or more
Required space
When closing the discharge grill, the required space is
30mm or more. (Note 3)
790 Suspension position
1000mm or more (Requierd space)
Height of suspension bracket
Suspension bolt
4-M3~M10
NOTES
1
Location for manufacture’s label: on bell mouth.
2
This is where the signal of infrared remote control is received.
Refer to the drawing of infrared remote control in detail.
3
When closing the discharge grill (2 or 3 way discharge), direction of pipe
connection will be limited, please refer to Installation manual..
Nr
Part name
Description
1
Liquid pipe connection
ø9.5 Flare connection
2
Gas pipe connection
ø15.9 Flare connection
3
Drain pipe connection
VP20
4
Air outlet
5
Air suction grille
6
Corner decoration cover
7
Right pipe/wiring connection
8
Rear pipe/wiring connection
9
Pipe through cover
10 Accessory drain elbow