• Indoor Units • 4-WAY BLOW CEILING SUSPENDED CASSETTE • BEVQ-MAVE
• VRV Systems • Indoor Units
14
11
Junction box - BEVQ-MAVE
11 - 1 Specifications
3
In
do
or
U
ni
t
VR
V
Sy
st
em
s
BE
VQ
-M
AV
E
4-
Wa
y
Bl
ow
11-1-1Technical Specifications
BEVQ71MAVE
BEVQ100MAVE
BEVQ125MAVE
Power input
(Nominal)
Cooling
kW
0.189
0.298
0.298
Heating
kW
0.169
0.278
0.278
Casing
Material
Galvanised steel plate
Dimensions
Packing
Height
mm
100
100
100
Width
mm
350
350
350
Depth
mm
225
225
225
Sound absorbing thermal insulation material
Flame and heat resistant foamed polyetherene
Weight
Unit
kg
3.0
3.0
3.5
Indoor Units
Liquid (OD)
Type
Flare connection
Diameter mm
9.5
9.5
9.5
Gas
Type
Flare connection
Diameter mm
15.9
15.9
15.9
Outdoor Unit
Liquid (OD)
Type
Flare connection
Diameter mm
9.5
9.5
9.5
Suction gas
(OD)
Type
Flare connection
Diameter mm
15.9
15.9
15.9
Standard
Accessories
Item
Installation manual
Gas piping connections
Insulation for fitting
Sealing material
Clamps
11-1-2Electrical Specifications
BEVQ71MAVE
BEVQ100MAVE
BEVQ125MAVE
Power Supply
Name
VE
Phase
1˜
Frequency
Hz
50/60
Voltage
V
220-240
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Total circuit
Minimum circuit amps
(MCA)
A
0.8
1.3
1.3
Maximum fuse amps (MFA) A
15
15
15
Notes
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA: MCA=1.25 X FLA
Select wire size based on MCA
Instead of a fuse, use a circuit breaker
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A