English
3
Do not wash the air conditioner or the remote
controller with water, as this may result in elec-
tric shocks or fire.
Do not install the air conditioner at any place
where there is a danger of flammable gas leak-
age.
In the event of a gas leakage, build-up of gas near
the air conditioner may result in fire hazards.
Do not put flammable containers, such as
spray cans, within 1 m from the blow-off
mouth.
The containers may explode because the warm air
output of the indoor or outside unit will affect them.
Arrange the drain to ensure complete drain-
age.
If proper drainage from the outside drain pipe does
not occur during air conditioner operation, there
could be a blockage due to dirt and debris build-up
in the pipe.
This may result in a water leakage from the indoor
unit. Under these circumstances, stop air condi-
tioner operation and consult your dealer for assis-
tance.
Do not let children play on or around the out-
side unit.
If they touch the unit carelessly, injury may be
caused.
Do not place water containers (flower vases,
etc.) on the unit, as this may result in electric
shocks or fire.
Consult your dealer regarding cleaning the
inside of the air conditioner.
Improper cleaning may cause breakage of plastic
parts, water leakage and other damage as well as
electric shocks.
To avoid injury, do not touch the air inlet or alu-
minium fins of the unit.
Do not place the controller exposed to direct
sunlight.
The LCD display may get discolored, failing to dis-
play the data.
Do not wipe the controller operation panel with
benzine, thinner, chemical dustcloth, etc.
The panel may get discolored or the coating
peeled off. If it is heavily dirty, soak a cloth in water-
diluted neutral detergent, squeeze it well and wipe
the panel clean. And wipe it with another dry cloth.
Never touch the internal parts of the controller.
Do not remove the front panel. Touching certain
internal parts will cause electric shocks and dam-
age to the unit. Please consult your dealer about
checking and adjustment of internal parts.
Do not leave the remote controller wherever
there is a risk of wetting.
If water gets into the remote controller there is a
risk of electrical leakage and damage to electronic
components.
Never press the button of the remote controller
with a hard, pointed object.
The remote controller may be damaged.
Never pull or twist the electric wire of a remote
controller.
It may cause the unit to malfunction.
Do not operate the air conditioner when using
a room fumigation - type insecticide.
Failure to observe could cause the chemicals to
become deposited in the unit, which could endan-
ger the health of those who are hypersensitive to
chemicals.
The appliance is not intended for use by unat-
tended young children or infirm persons.
Impairment of bodily functions and harm to health
may result.
Children should be supervised to ensure that they
do not play with the unit or its remote controller.
Accidental operation by a child may result in
impairment of bodily functions and harm health.
Do not place objects in direct proximity of the
outside unit and do not let leaves and other
debris accumulate around the unit.
Leaves are a hotbed for small animals which can
enter the unit. Once in the unit, such animals can
cause malfunctions, smoke or fire when making
contact with electrical parts.
Watch your steps at the time of air filter clean-
ing or inspection.
High-place work is required, to which utmost
attention must be paid.
If the scaffold is unstable, you may fall or topple
down, thus causing injury.
2. SPECIFICATIONS
Model
System name
Independent unit
RWEYQ8PY1
RWEYQ8PY1
RWEYQ10PY1
RWEYQ10PY1
RWEYQ16PY1
RWEYQ8PY1
RWEYQ8PY1
Power supply
Phase
-
3N
~
3N
~
3N
~
Frequency
(Hz)
50
50
50
Voltage
(V)
380-415
380-415
380-415
Nominal cooling capacity
(kW)
22.4
26.7
44.8
Nominal heating capacity
(kW)
25.0
31.5
50.0
Dimensions H×W×D
(mm)
1000×780×550
1000×780×550
1000×780×550
+1000×780×550
Mass
(kg)
149
150
149+149
Refrigerant
type
-
R410A
R410A
R410A
charge
(*1)
(kg)
3.5
4.2
3.5+3.5
Design pressure
refrigerant high side
(bar)
40
40
40
(MPa)
4.0
4.0
4.0
refrigerant low side
(bar)
25
25
25
(MPa)
2.5
2.5
2.5
water side
(bar)
19.6
19.6
19.6
(MPa)
1.96
1.96
1.96
01_EN_3P153897-7L.fm Page 3 Friday, July 11, 2008 1:58 PM