• If the piping length between the outdoor units exceeds 6.5 ft. (2 m),
create a rise of 8 in. (200 mm) or more in the suction gas and high/
low pressure gas line within a length of 6.5 ft. (2 m) from the kit.
If ≤ 6.5 ft. (2 m)
1
2
a
If > 6.5 ft. (2 m)
1
a
a
b
2
c
c
b
1 To indoor units
2 Piping between outdoor units
a
≤ 6.5 ft. (2 m)
b
≥ 8 in. (200 mm)
c > 6.5 ft. (2 m)
NOTE
There are restrictions on the refrigerant pipe connection order be-
tween outdoor units during installation in case of a multiple outdoor
unit system. Install according to following restrictions. The capacities
of outdoor units A, B and C must fulfill the following restriction condi
-
tions: A≥B≥C.
A
B
C
1 2
3
1 To indoor unit
2
Outdoor unit multi connecting piping kit (first branch)
3 Outdoor unit multi connecting piping kit (second branch)
8.2.6. Branching the refrigerant piping
1
For installation of the refrigerant branch kit, refer to the installation
manual delivered with the kit.
A
B
1
1
-30°
+30°
Horizontal
Vertical
1 Horizontal surface
• Mount the REFNET joint so that it branches either horizontally or vertically.
• If mounted horizontally, do not tilt the joint more than 30° above or
below the horizontal plane.
• Mount the REFNET header so that it branches horizontally.
2
Installation of the multi connection piping kit.
1
B
1
C
D
+15°
-15°
A
C > 4-3/4 in. (120 mm)
D > 19-11/16 in. (500 mm)
• Install the joints horizontally, so that the caution label (1) attached to
the joint comes to the top.
- Do not tilt the joint more than 15° above or below the horizontal
plane (see view A).
- Do not install the joint vertically (see view B).
• Make sure that the total length of the piping connected to the joint
is absolute straight for more than 19-11/16 in. (500 mm). Only if a
straight field piping of more than 4-3/4 in. (120 mm) is connected,
more than 19-11/16 in. (500 mm) of straight section can be ensured.
• Improper installation may lead to malfunction of the outdoor unit.
8.3. Guidelines for handling stop valve
8.3.1. Cautions on handling the stop valve
• Make sure to keep all stop valves open during operation.
•
The figure below shows the name of each part required in handling the stop valve.
• The stop valves are factory closed.
• When handle the stop valves, be careful not to damage the port
pipes around (refer to P22).
3
4
1
2
1 Service port and service port
cover
2 Stop valve
3 Field piping connection
4 Stop valve cover
1
2
3
4
5
1 Service port
2 Cap
3 Hexagon hole
4 Shaft
5 Seal