Service Check Function
SiUS331604E
129
Service Diagnosis
3.3
Error Codes and Descriptions
k
: ON
h
: OFF
l
: Blink
Error code
Operation
lamp
Description
Reference
Page
Indoor Unit
A0
l
External protection device abnormality
A1
l
Indoor unit PCB abnormality
A3
l
Drain level control system (S1L) abnormality
A6
l
Indoor fan motor (M1F) lock, overload
Indoor fan motor abnormality
Overload/overcurrent/indoor fan motor lock
A7
k
Swing flap motor abnormality
A8
l
Power supply voltage abnormality
A9
l
Electronic expansion valve coil abnormality, Dust clogging
AF
k
Drain level above limit
AJ
l
Capacity determination device abnormality
C1
l
Transmission abnormality (between indoor unit PCB and fan PCB)
C4
l
Heat exchanger liquid pipe thermistor abnormality
C5
l
Heat exchanger gas pipe thermistor abnormality
C6
l
Combination abnormality (between indoor unit PCB and fan PCB)
C9
l
Suction air thermistor (R1T) abnormality
Remote sensor abnormality
CA
k
Discharge air thermistor abnormality
CC
k
Humidity sensor system abnormality
CE
k
Infrared presence/floor sensor error
CJ
k
Remote controller thermistor abnormality
Outdoor Unit
E1
l
Outdoor main PCB abnormality
E3
l
Activation of high pressure switch
E4
l
Activation of low pressure sensor
E5
l
Inverter compressor motor lock
E7
l
Outdoor fan motor abnormality
E9
l
Electronic expansion valve coil abnormality
F3
l
Discharge pipe temperature abnormality
F6
l
Refrigerant overcharged
H9
l
Outdoor air thermistor abnormality
J3
l
Discharge pipe thermistor abnormality
J5
l
Suction pipe thermistor abnormality
J6
l
Outdoor heat exchanger deicer thermistor abnormality
J7
l
Outdoor heat exchanger liquid pipe thermistor abnormality
J9
l
Subcooling heat exchanger gas pipe thermistor abnormality
JA
l
High pressure sensor abnormality
JC
l
Low pressure sensor abnormality
L1
l
PCB (for inverter compressor) abnormality
L4
l
Radiation fin temperature rise abnormality
L5
l
Inverter compressor instantaneous overcurrent
L8
l
Inverter compressor overcurrent
L9
l
Inverter compressor startup abnormality
LC
l
Transmission error (between microcomputers on the outdoor main PCB)
P1
l
Inverter circuit capacitor high voltage
P4
k
Radiation fin thermistor abnormality
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...