Troubleshooting by Error Code
SiUS331604E
187
Service Diagnosis
4.35 Transmission Error (Between Microcomputers on the
Outdoor Main PCB)
Error Code
LC
Applicable
Models
All outdoor units
Method of Error
Detection
Transmission conditions between microcomputers on the outdoor main PCB are tested via
microcomputer.
Error Decision
Conditions
No normal transmission after a certain period of time
Supposed
Causes
Connection error between microcomputers on the outdoor main PCB
Defective outdoor main PCB (Transmission part)
Defective noise filter
External factors (Noise, etc.)
Defective inverter compressor
Defective fan motor
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
Replace the outdoor
main PCB.
Replace the inverter
compressor.
YES
YES
NO
NO
YES
Replace the fan motor.
No
LC
error. Check
the error code again.
NO
Is the outdoor
main PCB
damaged?
Inverter
compressor insulation
resistance is less than
100 k
Ω
.
Fan motor
insulation resistance is
less than 1 M
Ω
.
Normal monitoring
light (green) of outdoor main
PCB (A1P) blinks.
YES
Replace the outdoor
main PCB.
Normal
monitoring light
(green) of inverter
PCB blinks.
( )
Keep operating.
Possibly because of
sudden power failure, etc.
NO
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...