SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
146
4.6
Overload/Overcurrent/Indoor Fan Motor Lock
Error Code
A6
Applicable
Models
FXMQ-M
Method of Error
Detection
This error is detected by detecting that the individual power supply for the fan turns OFF.
Error Decision
Conditions
When it is not detected that the individual power supply for the indoor fan turns ON while in
operation.
Supposed
Causes
Defective power supply for the indoor unit fan motor
Clogged drain piping
Actuation of the indoor unit safety device
Defective contact in the fan wiring circuit
Troubleshooting
Properly connect the cable.
NO
YES
YES
Is the
power supply
cable of the indoor
unit fan properly
connected?
NO
Is the fan
normally running?
Restart the fan.
Replace the indoor unit PCB.
It is supposed that the indoor
unit fan motor stops running
due to overload, overcurrent, or
lock.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...