SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
154
4.12 Transmission Abnormality (between Indoor Unit PCB and
Fan PCB)
Error Code
C1
Applicable
Models
FXMQ-PB
Method of Error
Detection
Transmission conditions between the indoor unit main PCB (A1P) and fan PCB (A2P) are checked
via micro-computer.
Error Decision
Conditions
When normal transmission is not carried out for a certain duration.
Supposed
Causes
Defective connection of the connector between indoor unit main PCB (A1P) and fan PCB (A2P)
Defective indoor unit main PCB (A1P)
Defective fan PCB (A2P)
External factor, such as instantaneous power failure