Troubleshooting by Error Code
SiUS331604E
185
Service Diagnosis
4.33 Inverter Compressor Overcurrent
Error Code
L8
Applicable
Models
All outdoor units
Method of Error
Detection
Error is detected by current flowing in the power transistor.
Error Decision
Conditions
Overload in the compressor is detected.
Supposed
Causes
Compressor overload
Broken wire inside compressor
Defective PCB
Disconnection of compressor
Troubleshooting
NO
YES
YES
NO
Check if the
compressor lead wires are
normal.
Insulation
resistance of the
compressor is 100 k
Ω
or below.
YES
NO
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Compressor coils are
disconnected.
Connect the compressor lead
wires then restart the operation.
CHECK 4
Check if the power transistor
is normal.
YES
Replace the compressor
lead wires.
Replace the inverter
compressor.
Replace the inverter
compressor.
Replace the
outdoor main PCB
(A1P).
NO
YES
Error code
L8
is
displayed again.
Continue the operation.
Inspection of the
compressor.
CHECK 4
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...