24.2 Procedure for Checking Maximum Concentration
Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.
Step1: Calculate the amount of refrigerant (lbs.) charged to each system separately.
Amount of refrigerant in a single unit
system (amount of refrigerant with
which the system is charged before
leaving the factory)
+
Additional charging amount (amount
of refrigerant added locally in
accordance with the length or diameter
of the refrigerant piping)
= Total amount of refrigerant (lbs.)
in the system
Note:
Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of
refrigerant with which each separate system is charged.
Step 2: Calculate the smallest room volume (ft.
3
)
In case like the following, calculate the volume of (a), (b) as a single room or as the smallest room.
(a) Where there are no smaller room divisions.
(b) Where there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth.
Opening between
rooms
Partition
(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15%
or more of the floor area.)
(c) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will
become the measurement target.
Summary of Contents for VRV IV REYQ-TAYCA
Page 1: ...EDUS371706C D 202002 Engineering Data Heat Recovery 60 Hz Design Manual REYQ TAYCA 575 V ...
Page 2: ......
Page 27: ...25 REYQ TAYCA EDUS371706C D 10 Dimensions REYQ72 168TAYCA C 3D107340A ...
Page 32: ...30 REYQ TAYCA EDUS371706C D 12 Center of Gravity REYQ72 120TAYCA 4D107384 ...
Page 33: ...31 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 4D107385 ...
Page 35: ...33 REYQ TAYCA EDUS371706C D 14 Piping Diagrams REYQ72 120TAYCA 3D107166 ...
Page 36: ...34 REYQ TAYCA EDUS371706C D REYQ144 168TAYCA 3D107167 ...
Page 43: ...41 REYQ TAYCA EDUS371706C D 18 Operation Limits REYQ72 384TAYCA 3D107375 ...
Page 45: ...43 REYQ TAYCA EDUS371706C D 20 Sound Levels Reference Data REYQ72TAYCA 4D107379B ...
Page 46: ...44 REYQ TAYCA EDUS371706C D REYQ96TAYCA 4D107380A ...
Page 47: ...45 REYQ TAYCA EDUS371706C D REYQ120TAYCA 4D107381A ...
Page 48: ...46 REYQ TAYCA EDUS371706C D REYQ144TAYCA 4D107382A ...
Page 49: ...47 REYQ TAYCA EDUS371706C D REYQ168TAYCA 4D107383A ...
Page 58: ...56 REYQ TAYCA EDUS371706C D 3P558142 1B ...
Page 59: ...57 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 60: ...58 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 61: ...59 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 62: ...60 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 63: ...61 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 64: ...62 REYQ TAYCA EDUS371706C D 1P385984 1A ...
Page 65: ...63 REYQ TAYCA EDUS371706C D Collective Indications Label 3P385987 1A ...
Page 66: ...64 REYQ TAYCA EDUS371706C D 3P385987 1A ...
Page 77: ......
Page 78: ......
Page 79: ......